Thermostat Setup Menus

The thermostat must be setup for the correct HVAC system type for proper opera  on.

Preset HVAC System se

ƫ

  ngs

The thermostat is preset for the following typical HVAC system con

fi

 gura  on:

•  HVAC system type: Standard gas/electric

•  HVAC fan type: Gas heat

• HVAC hea  ng stages: one

•  HVAC cooling stages: one

If the thermostat is installed on this type HVAC system, the System Setup does not need to be 
changed. 
If installed on a Heat Pump HVAC system or any HVAC con

fi

 gura  on other than the preset se   ngs, 

change the se   ngs in the SYSTEM setup menu to match the HVAC system.

NOTE:

 To conserve ba  ery life, the thermostat backlight turns o

  a  er a short   me of no ac  vity. 

The 

fi

 rst press of any bu   on turns on the backlight (but does not ini  ate any ac  on). Press the bu  on 

again to ini  ate the ac  on desired. If the backlight is already on, bu  on presses work with the 

fi

 rst 

press.

Wait Mode 

The thermostat has a Minimum O

  Time (MOT) delay a  er any hea  ng or cooling cycle ends. This 

delay prevents rapid hea  ng/cooling cycles and also provides “short cycle protec  on” for the system 
compressor. This delay may be no  ceable when you change a setpoint and it does not respond 
immediately due to the MOT delay   mer preven  ng the system from restar  ng. The MOT delay   me 
can be adjusted in the Advanced Se   ngs menu of the thermostat but there is a minimum of 

fi

 ve 

minutes delay to assure compressor protec  on.

Minimum Run Time (MRT)

The thermostat has a Minimum Run Time delay a  er the start of any hea  ng or cooling call. This 
minimum run   me assures even hea  ng and cooling cycles. The MRT will keep the system on, even 
if it reaches the setpoint room temperature, or you change the setpoint to a temperature that would 
sa  sfy the call, un  l the MRT expires. Changing the Mode to OFF will cancel the MRT and the system 
will turn o

   immediately. The MRT can be adjusted in the Advanced Se   ngs menu of the thermostat.

NOTE:

 The MRT delays are shown by 

fl

 ashing heat or cool icons on the display.

Содержание Gocontrol GC-TBZ48L

Страница 1: ...TBZ48L P N 10006936 C INK BLACK MATERIAL 20 LB MEAD BOND SIZE 8 500 X 5 500 TOL 0 125 SCALE 1 1 FOLDING ALBUM FOLD BINDING SADDLE STITCH NOTE To take full advantage of this device s Z Wave control capability you must purchase a compa ble Z Wave hub controller Remote control capability is provided via the hub controller s remote control app so ware ...

Страница 2: ... Standard HVAC systems only 13 Changeover Type For Heat Pump HVAC Systems Only 13 Z Wave Plus Installa on 14 Inclusion and Exclusion 14 Advanced Z Wave Information 15 Support for Associa on Groups 15 Clock Menu 15 Se ng the Clock 15 INFO Menu 16 Advanced System Se ngs Menu 17 Thermostat Opera on 19 Main Thermostat Screen 19 Backlight and Bu on Opera on 19 Display 19 Staging Indicators 19 Se ng the...

Страница 3: ...s Include A fixed format display with white backlight Hea ng and cooling setup display op ons System mode OFF Heat Cool Auto E Heat Fan mode control and display Auto ON Changeover type for Heat Pump HP systems On screen setup of HVAC type Fan type F C mode and sensor calibra on Compatible with 24 VAC gas oil or electric heating and air conditioning systems or gas millivolt heating systems DO NOT U...

Страница 4: ... WHITE ORANGE GREEN YELLOW BLACK BROWN THERMOSTAT BACK PANEL INTERNAL RC RH JUMPER C WIRE IS NOT REQUIRED FOR BATTERY OPERATION C WIRE IS REQUIRED FOR 24VAC OPERATION DEFAULTTHERMOSTAT SETUP TYPE STANDARD HVAC FAN GAS HEAT 1 STAGE HEATING 1 STAGE COOLING NO SETUP CHANGE REQUIRED FOR THIS CONFIGURATION Y2 Y1 G RC C RH W1 W2 FOR SINGLE TRANSFORMER SYSTEMS CONNECT R WIRE TO EITHER RC OR RH TERMINAL F...

Страница 5: ...AC SYSTEM BLUE RED WHITE ORANGE GREEN YELLOW BLACK BROWN THERMOSTAT BACK PANEL Y2 Y1 G R C R W1 O INTERNAL R R JUMPER C WIRE IS NOT REQUIRED FOR BATTERY OPERATION BATTERIES ARE NOT REQUIRED FOR 24VAC POWERED SYSTEMS CONNECT THE R WIRE TO EITHER R TERMINAL R R ARE JUMPERED TOGETHER INTERNALLY NOTE IF HEATING IS OCCURING WHEN COOOLING IS EXPECTED OR VICE VERSA CHANGE THE CHANGEOVER TYPE TO THE OPPOS...

Страница 6: ...ire typically a red wire BaƩery Power Powering the thermostat from ba eries does not require a C wire connec on DO NOT install ba eries if the thermostat is powered by 24VAC They are not required for backup If the thermostat is powered by ba eries the thermostat will operate for approximately 2 two years on four 4 AA Alkaline ba eries depending on the frequency of user opera ons and backlight oper...

Страница 7: ...shooting later if needed Terminal Typical Wire Color Function Y YELLOW Cool W WHITE Heat G GREEN Fan R RED 24VAC Return C BLUE 24V Common typically BLUE When the wire is present the thermostat can be powered without ba eries When the wire is absent the thermostat must be powered by ba eries if 24VAC is present across the R C wires Wiring Colors While the thermostat terminal markings are intended t...

Страница 8: ...anel of thermostat Mount the thermostat back panel on the wall See Figure 4 1 Use the two 2 wall anchors and two 2 Phillips screws provided to mount the back panel 2 Level as needed Figure 4 Mounting the Back Panel BACK PANEL BODY WITH PCB PUSH ON THUMB TAB TO RELEASE BACK PANEL Y2 Y1 G RC C RH W1 W2 Standard Y2 Y1 G R C R WI 0 Heat Pump ANCHORS 2 PROVIDED PHILLIPS SCREWS 2 PROVIDED ...

Страница 9: ...hese are internally jumpered together If installing a Standard HVAC system connect the wires from the HVAC system to the corresponding terminals on the thermostat back terminal block Use the table below as a guideline for connec ng the wires Wire Terminal Y Connect to the Y1 terminal G Connect to the G terminal R Connect to either RC or RH terminals Except for Dual Transformer Systems See Next Pag...

Страница 10: ...elow as a guideline for connec ng the wires Wire Terminal Y2 Connect to the Y2 terminal 2 stage systems only Y or Y1 Connect to the Y1 terminal G Connect to the G terminal COOL Rc Connect to RC terminal C Connect to C terminal Cooling System C Wire NOT Hea ng System C Wire HEAT Rh Connect to RH terminal W or W1 Connect to W1 terminal W2 Connect to W2 terminal 2 stage system only IMPORTANT FOR SEPA...

Страница 11: ...rminal Y Connect to the Y1 terminal G Connect to the G terminal R Connect to either R terminal C Connect to the C terminal The C wire 24VAC common Heat Pump systems typically have the C wire connected to the thermostat If there is no C wire ba eries MUST be installed W Connect to the W1 terminal O or B Connect to the O terminal Heat Pump setup must set changeover valve to correct O or B se ng See ...

Страница 12: ...nts on bo om of case See Figure 12 Install the four 4 type AA ba eries and assemble as shown in Fig 13 Figure 12 Opening Battery Case Cover Figure 13 Battery Installation MODE MODE FAN FAN BODY FRONT PANEL BACK PANEL MOUNTED TO WALL HOOK ON CATCH IN TOP OF BACK PANEL SNAP ONTO CATCHES AT BOTTOM OF BACK PANEL FRONT PANEL BACK PANEL MODE FAN BACK PANEL BODY ATTACHED TO WALL FRONT PANEL BATTERY COMPA...

Страница 13: ...h the first press Wait Mode The thermostat has a Minimum Off Time MOT delay a er any hea ng or cooling cycle ends This delay prevents rapid hea ng cooling cycles and also provides short cycle protec on for the system compressor This delay may be no ceable when you change a setpoint and it does not respond immediately due to the MOT delay mer preven ng the system from restar ng The MOT delay me can ...

Страница 14: ...e bu ons to scroll through the following menu items Figure 15 Menu Navigation The following menu items are displayed in order SETUP user preference se ngs SYSTEM HVAC system setup Z WAVE install uninstall from Z Wave network CLOCK set me and day INFO firmware versions and Z Wave network informa on MODE FAN Select Done Setup PRESS DONE TO EXIT BACK TO THE MAIN THERMOSTAT SCREEN PRESS SELECT TO ENTE...

Страница 15: ...he hea ng system type For Gas heat select GAS This is the default se ng For Electric heat press the bu ons to change to ELECTRIC Press SELECT to set Press DONE to exit Changeover Type For Heat Pump HVAC Systems Only The changeover or reversing valve is used to change from hea ng to cooling opera on The HVAC system is either a Changeover with Cooling type O or Changeover with Hea ng type B Most are...

Страница 16: ...add thermostat to network 7 Display line should flash WAIT then SUCCESS if Z Wave connec on is made 8 If Z Wave does not connect to controller WAIT then FAIL will flash in status display line 9 If thermostat fails to connect repeat Steps three 3 thru 7 to re try connec ng Your controller will indicate the thermostat was successfully added to its network see your controller s user manual for detail...

Страница 17: ...PORT THERMOSTAT_SETPOINT_REPORT THERMOSTAT_SETPOINT_MODE THERMOSTAT_FANMODE_REPORT THERMOSTAT_FANSTATE_REPORT THERMOSTAT_OPERATINGSTATE_REPORT THERMOSTAT_CONFIGURATION_REPORT Group 2 AssociaƟon Alerts will send a BASIC_SET 0xFF when a Cool Call starts and a BASIC_SET 0x00 when the Cool Call ends Group 3 AssociaƟon Alerts will send a BASIC_SET 0xFF when a Heat Call starts and a BASIC_SET 0x00 when ...

Страница 18: ...ugh the various items MODEL GC TBZ48L VERSION Thermostat firmware version ZWAVE Z Wave firmware version NODE ID Z Wave Node ID HOME ID Z Wave Home ID SYSTEM TYPE displays current System Type se ng If System Type Standard FAN TYPE displays current Fan Type se ng If System Type Heat Pump CHANGEOVER TYPE displays current Change Over se ng ...

Страница 19: ... Y or N N Aux Heat Enable Heat Pump Systems only Enables the auxiliary heat opera on Typically the auxiliary heat will be heat strips in a heat pump system Y or N N 2nd Stage Heat Enable Enables the second stage heat opera on Y or N N 2nd Stage Cool Enable Enables the second stage cool opera on Y or N N Minimum run me Sets the Minimum Run Time MRT delay before a hea ng cooling cycle can turn off Se...

Страница 20: ...es 2 Hea ng Stage 2 Off Threshold Sets the delay from setpoint that stage 2 hea ng stops Stage 2 turns off at setpoint Delta Stage 2 0 to 6 degrees 0 Aux Heat On Threshold Sets the delta from setpoint that stage 3 hea ng starts 3 to 8 degrees 3 Aux Heat Off Threshold Sets the delta from setpoint that stage 3 hea ng stops Stage 3 turns off at setpoint Delta Stage 3 0 to 7 degrees 0 Cooling Stage 1 On T...

Страница 21: ...active displayed System is ON and cooling blinking System is ON and cooling Minimum Run Time MRT delay is active NOTE Degrees C Celsius are shown in 5 degree increments Degrees F Fahrenheit are shown in 1 degree increments Staging Indicators 1 Stage 1 hea ng or cooling is ON 2 Stage 2 hea ng or cooling is ON 3 Stage 3 hea ng Aux Heat is ON For Heat Pump systems only Heat E Emergency heat mode ac v...

Страница 22: ...l system mode Heat E for Emergency Heat will be displayed if the HVAC System Type is set to Heat Pump If there is a compressor failure with the Heat Pump system se ng the mode to Emergency Heat will allow the supplemental Aux Heat to come on first whenever there is a call for hea ng It also disables the compressor output to prevent further damage to the HVAC system CAUTION Emergency Heat should on...

Страница 23: ...ush the hea ng setpoint lower if the cooling setpoint is set below the current hea ng setpoint A 3 degree separa on is maintained between the hea ng and cooling setpoints The same is true for raising the hea ng setpoint above the cooling setpoint The thermostat will push the cooling setpoint up to maintain the 3 degree separa on MODE FAN 74 Off Auto PRESS EITHER BUTTON TO GO TO THE SETPOINT CHANGE...

Страница 24: ... Use the FAN bu on to select the HVAC system s fan mode Auto Fan automa cally operated by the HVAC system normal se ng On Manual Fan mode Fan stays on un l mode is changed back to Auto independent of the hea ng or cooling system opera on MODE FAN 74 Off Auto PRESS FAN FOR ON OR AUTOMATIC MODE ...

Страница 25: ...ut can be set to 0 which will keep the backlight on con nuously SENSOR CALIBRATION Change the temperature calibra on by 7 degrees Press the UP or DOWN arrow bu ons to change to the desired display temperature STATUS LINE Sets Status Line to Setpoints or Clock mode MODE FAN 74 Off Auto TO SELECT THE MENU MODE PRESS AND HOLD THE FAN BUTTON UNTIL THE SETUP SCREEN IS DISPLAYED MODE FAN Select Done Set...

Страница 26: ...ID SYSTEM TYPE displays current System Type se ng If System Type Standard FAN TYPE displays current Fan Type se ng If System Type Heat Pump CHANGEOVER TYPE displays current Change Over se ng Ba ery xx Ba ery Level If ba ery powered Factory Reset WARNING Please use this procedure only when the Z Wave Primary Controller is missing or otherwise inoperable To reset the TBZ48L s Z Wave parameters to Fa...

Страница 27: ...able 4 0 Disabled 1 Enabled 0 Disabled 1 Enabled 7 C F Type 0 Cen grade 1 Fahrenheit 0 Cen grade 1 Fahrenheit 8 MOT 5 5 9 5 9 9 MRT 5 3 9 3 9 10 Setpoint H C Delta 3 15 3 15 11 H Delta Stage 1 ON 1 6 1 6 12 H Delta Stage 1 OFF 0 5 0 5 13 H Delta Stage 2 ON 2 7 2 7 14 H Delta Stage 2 OFF 0 6 0 6 15 H Delta Aux ON 3 8 3 8 16 H Delta Aux OFF 0 7 0 7 17 C Delta Stage 1 ON 1 6 1 6 18 C Delta Stage 1 OF...

Страница 28: ...24 Display Lock 3 0 unlocked 1 locked 0 unlocked 1 locked 26 Backlight Timer 10 30 10 30 33 Max Heat Setpoint 30F 109F 30F 109F 34 Min Cool Setpoint 33F 112F 33F 112F 38 Schedule Enable 0 Disabled 1 Enabled 0 Disabled 1 Enabled 39 Run Hold Mode3 7 0 Hold 1 Run 0 Hold 1 Run 40 Setback Mode 3 0 No Setback 2 Un Occupied Mode 0 No Setback 2 Un Occupied Mode 41 Un Occupied HSP 1 30F 109F 30F 109F 42 Un...

Страница 29: ...ions 5 75 146mm W 4 5 114 3mm H 1 00 25 4mm D Screen Size 2 7 X 1 4 LCD w white backlight 68 6mm X 35 6mm Buttons 4 mechanical bu ons Mode Fan Up Arrow Down Arrow Certification FCC Part 15 Industry Canada Regulatory Information FCC ID WIBTZW011 ThisdevicecomplieswithPart15oftheFCCRules Opera onissubjecttothefollowingtwocondi ons 1 This devicemaynotcauseharmfulinterference and 2 Thisdevicemustaccep...

Страница 30: ...ssories electrical power problems or surges impact by foreign objects accident fire acts of God normal wear and tear or shipping damage other than a shipment from NS C Note that all NS C products are designed to be installed removed and serviced by trained individuals or professionals Keep your original sales receipt as it will be required to obtain warranty service This warranty shall not be exte...

Страница 31: ...Copyright 2017 Nortek Security Control LLC 29 ...

Страница 32: ...10006936 C ...