Appendix-B
Nortec EL/RS Outdoor
2584597_B_EN_1705
B
Appendix
B.1
Installation Checklist
The following is a consolidated installation checklist that can be used in the commissioning of the unit:
Mounting
Unit mounted in an outdoor environment where it is not exposed to severe weather, or where the
temperature drops below -40 °F (-40 °C), and where the wind speed does not exceed 100 mph
(160 km/h)?
Adequate clearances maintained (according to
"Location and Suggested Clearances" on page 22
, and all
local and national installation codes)?
Mounting surface stable and reinforced to support the full operating weight of the humidifier?
Unit level?
Unit fastened securely?
Steam Line
Total system backpressure does not exceed 5.5 in H2O (1.37 kPa)?
Steam line maintain constant minimum upslope of 10° or downslope of 2°? If steam line runs upward,
is a condensate trap installed at the location where the steam exits the unit? Condensate line and
trap trace heated?
Steam line sized correctly, and does not exceed maximums specified in the Nortec EL/RS manuals?
Minimum bend radius of 12 in (300 mm) for steam hose, or 5× internal diameter for rigid pipes
maintained?
Steam line does not reduce in diameter except at the steam distributor? Condensate line installed
just before the restriction?
Steam lines do not merge except at the steam distributor through a Nortec adaptor?
Steam line does not sag or kink? Supported adequately? Condensate trap installed at all low points
in line?
If a steam hose is used, is it attached securely with clamps? Clamps secure without crushing steam
line?
Allowances for thermal expansion during operation, and shortening of the hose due to aging taken
into consideration?
Steam line properly insulated?
Steam line purged?
Condensate Line
Drain water temperature meet local code requirements?
Condensate line from the steam distributor condensate port connected to the humidifier fill cup port,
or the drain?
Condensate lines installed at all low points, and at horizontal -to-vertical transitions in the steam line?
Condensate lines in the steam line always connect to full-size "T" connectors?
Condensate traps have a minimum loop height of 8 in (200 mm) and installed at least 12 in (300
mm) below the "T" connector or steam distributor?
All condensate lines have a constant minimum downslope of 1 in/48 in (1.2°)?
Maximum distance between the condensate traps on long runs 15 ft (4.5 m)?
Содержание EL SERIES
Страница 10: ...6 Receiving and Storage 2584597_B_EN_1705 Nortec EL RS Outdoor This page intentionally left blank ...
Страница 16: ...12 Product Overview 2584597_B_EN_1705 Nortec EL RS Outdoor This page intentionally left blank ...
Страница 46: ...42 Commissioning 2584597_B_EN_1705 Nortec EL RS Outdoor This page intentionally left blank ...
Страница 58: ...54 2584597_B_EN_1705 Nortec EL RS Outdoor This page intentionally left blank ...