Operation and Maintenance
7.1
Operating the Unit
The Nortec EL/RS Outdoor humidifier is operated in the same manner as its indoor counterpart. Refer
to respective Nortec EL/Nortec RS operation and maintenance manual for details.
7.2
Inspections During Operation
Regularly inspect the following when the unit is in operation:
Inspect the water, drain and steam connections for any leaks.
Make sure that the drain lines are not blocked or kinked, and empty into the air gap funnel inside
the building.
Check the unit and other system components have not shifted from their mountings, and are fas-
tened securely.
Visually check for any damage to the electrical wiring.
Visually check the heating wires and insulation around the water and drain lines for damage.
Inspect the heater and fan for buildup of dirt and pollen, and make sure that the air intake and ex-
haust shrouds are free of all blockages.
Check the Home screen on the unit for maintenance or alarm messages.
Note:
The remote fault
board can also be used to remotely monitor the unit for maintenance or alarm messages.
Check that the doors on the unit are closed and fastened securely.
In units operating in cold climates, inspect the external freeze protection system and make sure that
it is fully functional at all times. Refer to
"Freeze Protection System" on page 44
.
In units operating in cold climates, keep the area around the unit clear of snow and ice accumulation
to permit opening and closing of the front and side doors.
Содержание EL SERIES
Страница 10: ...6 Receiving and Storage 2584597_B_EN_1705 Nortec EL RS Outdoor This page intentionally left blank ...
Страница 16: ...12 Product Overview 2584597_B_EN_1705 Nortec EL RS Outdoor This page intentionally left blank ...
Страница 46: ...42 Commissioning 2584597_B_EN_1705 Nortec EL RS Outdoor This page intentionally left blank ...
Страница 58: ...54 2584597_B_EN_1705 Nortec EL RS Outdoor This page intentionally left blank ...