Essential Addresses and Address Content (continued)
Address
Address for
Admissible content
Note
DB15.DBX 10.0
Local service (LS)/on-
site/local operation
False = no local operation possible at the
PICO controller (LS = 0)
Lock symbol visible in the PICO
controller display
NOTE:
Writing parameters is
only possible with LS=false.
This command should be
cyclically sent no later than prior
to expiration of the LS Timeout
setting, otherwise the lock symbol
will disappear.
True = local operation at the PICO controller
possible (LS = 1)
DB15.DBX 10.1
Reading/writing
unlocked
False = data interchange PICO controller—
SPS blocked
True = data interchange PICO controller—SPS
unblocked
DB15.DBX 10.3
Error Status Flag Bus Message is coming from the PICO controller
Possible causes:
• TimeOut error from the PICO
controller
• PICO controller/ communicator
power OFF
• CAN/PROFIBUS cable
unplugged, damaged
False = PICO controller not available
True = PICO controller available
DB15.DBD 12
Value/Parameter
value
Refer to the “Value Range in the PROFIBUS
Project” column in the “Value Codes and
Admissible Value Ranges” table.
Parameter value written into this
address from PICO controller
DB15.DBX 80.1
Busy Status Flag
False = sending data not possible
Flag comes from PICO controller
and signalizes readiness to
receive
True = sending data possible
DB15.DBX 16.0
Write/read individual
values or write a
complete line
False = writing/reading individual values
possible; starting/stopping a channel possible
Set flag to “false” if setting
parameters above DB20
True = complete line is being written
Set flag to “true” if setting
parameters above DB19
DB16.DBX 18.3
Error status flag
parameterization
False = no error flag was set by the PICO
controller
Possible causes:
• Line value addressed with 100
• Channel value addressed with
1-99
• Channel address false
• Value range false
• Temperature range 100/200 °C
false
• Write access for LocalService
= True
• Start via PROFIBUS with Active
• Repeated start via PROFIBUS
with channel active
• Repeated stop via PROFIBUS
with channel inactive
True = error flag was set by the PICO
controller
PICO Controller 2+2-XCH-V3
81