![Nord Drivesystems SK 750E Series Скачать руководство пользователя страница 99](http://html1.mh-extra.com/html/nord-drivesystems/sk-750e-series/sk-750e-series_manual_1701261099.webp)
BU 0750 GB
Technical design subject to change
99
Parameter
Setting value / Description / Note
Parameter
set
Available with option
Digital functions:
All of the relay functions described in parameter P434 >Function relay 1< can be transmitted via the
analogue output as well. Whenever a condition is true, a voltage of 10.0V will be applied to the out-
put terminals. A negation of the function can be defined in parameter P419 >Scaling the analogue
output<.
15 =
External brake
16 =
Inverter is working
17 =
Current limit
18 =
Torque current limit
19 =
Frequency limit
20 =
Level with setpoint
21 =
Fault
22 =
Warning
23 =
Overcurrent warning
24 =
Mot.overtemp.warning
25 =
Torque current limit
26 =
Value of P541
27 =
Torq.curr. limit gen
28 =
... 29 not assigned
34 =
... 43 not assigned
44 =
Bus In Bit 0
45 =
Bus In Bit 1
46 =
Bus In Bit 2
47 =
Bus In Bit 3
48 =
Bus In Bit 4
49 =
Bus In Bit 5
50 =
Bus In Bit 6
51 =
Bus In Bit 7
52 =
Value Bus Setpoint
P419
Norm. analog outp. 1
P
STD
MLT
-500...500 %
[ 100 ]
Analog functions P418 (= 0 ... 14, 30, 31)
This parameter can be used to adjust the analogue output to the desired working range. The maxi-
mum analogue output (10V) will correspond to the scaled value of the option selected.
Consequently if the setting of this parameter is increased from 100% to 200% while the operating
point remains the same, the analogue output voltage is reduced by half. Accordingly a 10-volt output
signal will correspond to twice the nominal value.
Where negative values are concerned the logic is reversed. In that case a setpoint of 0% will be put
out as 10 volts at the output and a 100% setpoint as 0 volt.
Digital functions P418 (= 15 … 52)
This parameter can be used to set the switching threshold for the functions current limit (= 17),
torque current limit (= 18) and frequency limit (= 19). A 100% setting will be equivalent to the respec-
tive nominal value of the motor (see also P435).
If a negative value is selected the function assigned to the analogue output is put out as a negated
value (0/1 1/0).