SK 500E – Users Manual for Frequency Inverters
142
BU 0500 EN-3021
P534
[-01]
[-02]
Torque disconn. limit
(Torque disconnection limit)
S
P
0 ... 400 % / 401
{ all 401 }
Via this parameter both the
drive
[-01] and the
generator
[-02] switch-off value can be adjusted.
If 80% of the set value is reached, a warning status is set. At 100% switch-off is performed with
an error message.
Error 12.1 is given on exceeding the drive switch-off limit and 12.2on exceeding the generator
switch-off limit.
[01] =
drive switch-off limit
[02] =
generator switch-off limit
401 =
OFF
means that this function has been disabled.
Pos: 341 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P500-P599/Parameter P535 – I2t-Motor @ 2\mod_1346932169045_388.docx @ 43200 @ @ 1
P535
I
2
t Motor
(I
2
t Motor)
0 … 24
{ 0 }
The motor temperature is calculated depending on the output current, the time and the output
frequency (cooling). If the temperature limit value is reached then switch off occurs and error
message E002 (motor overheating) is output. Possible positive or negative acting ambient
conditions cannot be taken into account here.
The I
2
t motor function can be set in a differentiated manner. 8 characteristic curves with three
different triggering times (<5 s, <10 s and <20 s) can be set. The trigger times are based on
classes 5, 10 and 20 for semiconductor switching devices. The recommended setting for standard
applications is
P535=5
.
All curves run from 0 Hz to half of the nominal motor frequency (P201). The full nominal current is
available from half of the nominal frequency upwards.
With multi-motor operation the monitoring must be disabled.
0 = I
2
t Motor off
: Monitoring is inactive
NOTE:
Shut-off classes 10 and 20 are provided for applications with heavy starting. When
using these shut-off classes, it must be ensured that the FI has a sufficiently high
overload capacity.
Switch-off class 5,
60s at 1.5x I
N
Switch-off class 10,
120s at 1.5x I
N
Switch-off class 20,
240s at 1.5x I
N
I
N
at 0Hz
P535
I
N
at 0Hz
P535
I
N
at 0Hz
P535
100%
1
100%
9
100%
17
90%
2
90%
10
90%
18
80%
3
80%
11
80%
19
70%
4
70%
12
70%
20
60%
5
60%
13
60%
21
50%
6
50%
14
50%
22
40%
7
40%
15
40%
23
30%
8
30%
16
30%
24
Pos: 342 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P500-P599/Parameter P535 – I2t-Motor [Ergänzung SK 5xxE] @ 0\mod_1328093600385_388.docx @ 11617 @ @ 1
0 ... 1
{ 0 }
Up to and including software version 1.5 R1, the following applies:
0 =
Switched off
1 =
Switched on (equivalent to setting 5 (see above))
Pos: 343 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P500-P599/Parameter P536 – Stromgrenze @ 0\mod_1328093664510_388.docx @ 11640 @ @ 1
P536
Current limit
(Current limit)
S
0.1 ... 2.0 / 2.1
(x nominal current of
FI)
{ 1.5 }
The inverter output current is limited to the set value. If this limit value is reached, the inverter
reduces the actual output frequency.
Multiplier with the inverter nominal current, gives the limit value
2.1 = OFF
represents the disabling of this limit value.