SK 500E – Users Manual for Frequency Inverters
120
BU 0500 EN-3021
List of possible digital functions of the analog outputs
All relay functions described in parameter P434 can also be transferred via the analog output. If a
condition has been fulfilled, then there will be 10 V at the output terminals. Negation of the function
can be specified in parameter P419.
Value
Function
Value
Function
15
External brake
32
FI ready
16
Inverter working
33
Frequency and setpoint source
17
Current limit
34
... 40 reserved (POSICON
BU 0510)
18
Torque current limit
41
... 43 reserved
19
Frequency limit
44
BusIO In Bit 0
20
Setpoint reached
45
BusIO In Bit 1
21
Fault
46
BusIO In Bit 2
22
Warning
47
BusIO In Bit 3
23
Overcurrent warning
48
BusIO In Bit 4
24
Motor overtemperature warning
49
BusIO In Bit 5
25
Torque current limit active
50
BusIO In Bit 6
26
Value of P541
51
BusIO In Bit 7
27
Generator torque current limit
52
Value from Bus setpoint
Output via Bus (if P546, P547 or P548 = 19), BUS Bit 4
then controls the analog output.
28
... 29 reserved
60
reserved (PLC
BU 0550)
Pos: 248 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterüberschrift - Fortsetzung Tabelle @ 1\mod_1331566123473_388.docx @ 18340 @ @ 1
Parameter
{factory setting}
Setting value / Description / Note
Supervisor
Parameter
set
Pos: 249 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P400-P499/Parameter P419 – Normierung Analogausgang 1 [SK 500...535E] @ 0\mod_1327940918277_388.docx @ 9766 @ @ 1
P419
Scaling of analog output 1
(Scaling of analog output 1
)
P
-500 ... 500 %
{ 100 }
Analog functions P418 (= 0 ... 6 and 8 … 14, 30)
With this parameter an adjustment can be made to the analog output for the selected working
range. The maximum analog output (10 V) corresponds to the scaling value of the appropriate
selection.
Therefore, if this parameter is raised from 100 % to 200 % at a constant working point, the analog
output voltage is halved. The 10 Volt output signal then corresponds to twice the nominal value.
For negative values the logic is reversed. An actual value of 0 % will then produce 10 V at the
output and -100 % will produce 0 V.
Digital functions P418 (= 15 ... 28, 34...52)
The switching threshold can be set using this parameter for the functions Current limit (= 17),
Torque current limit (= 18) and Frequency limit (= 19). A value of 100% refers to the
corresponding motor nominal value (see also P435).
With a negative value, the output function is output negated (0/1
→
1/0).
Pos: 251 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P400-P499/Parameter P420 – Digitaleingang 1 [SK 500...535E] @ 0\mod_1327941071805_388.docx @ 9812 @ @ 1
P420
Digital input 1
(Digital input 1)
0 ... 74
{ 1 }
Enable right
as factory setting, control terminal 21 (DIN1)
Various functions can be programmed. These can be seen in the following table.
Pos: 253 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P400-P499/Parameter P421 – Digitaleingang 2 [SK 500...535E] @ 0\mod_1327941193596_388.docx @ 9858 @ @ 1