SK 500E – Users Manual for Frequency Inverters
136
BU 0500 EN-3021
P510
[-01]
[-02]
Setpoint source
(Setpoint source)
S
0 ... 10
{ all 0 }
Selection of the setpoint source to be parameterised.
[-01] =
Main
setpoint source
[-02] =
Auxiliary
setpoint source
Selection of the interface via which the FI receives the setpoint.
0 = Auto (=P509):
The source of the auxiliary setpoint is
automatically derived from the setting in the parameter
P509 >Interface<
1 = Control terminals
, digital and analog inputs control the
frequency, including fixed frequencies
2 = USS (
or
Modbus RTU
)
3 = CAN
4 = Profibus
5 = InterBus
6 = CANopen
7 = DeviceNet
8 = Ethernet TU
9 = CAN Broadcast
10 = CANopen Broadcast
Pos: 315 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P500-P599/Parameter P511 – USS-Baudrate @ 0\mod_1328092296926_388.docx @ 11134 @ @ 1
P511
USS baud rate
(USS baud rate)
S
0 ... 8
{ 3 }
Setting of the transfer rate (transfer speed) via the RS485 interface. All bus participants must
have the same baud rate setting.
SK 54xE and above:
0 =
4,800 Baud
4 =
57,600 Baud
1 =
9,600 Baud
5 =
115,200 Baud
2 =
19,200 Baud
6 =
187,750 Baud
3 =
38,400 Baud
7 =
230,400 Baud
8 =
460,800 Baud
NOTE:
For communication via Modbus a transfer rate of maximum 38400 Baud must be
set.
Pos: 316 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P500-P599/Parameter P512 – USS-Adresse @ 0\mod_1328092365912_388.docx @ 11157 @ @ 1
P512
USS address
(USS address)
0 ... 30
{ 0 }
Setting of the FI bus address for USS communication.
Pos: 317 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P500-P599/Parameter P513 – Telegrammausfallzeit [SK 5xxE] @ 0\mod_1328092407709_388.docx @ 11180 @ @ 1
P513
Telegram time-out
(Telegram time out)
S
-0.1 / 0.0 /
0.1 ... 1000 s
{ 0.0 }
Monitoring function of the active bus interface. Following receipt of a valid telegram, the next one
must arrive within the set period. Otherwise the FI reports an error and switches off with the error
message E010 >Bus Time Out<.
0.0 = Off
: Monitoring is switched off.
-0.1 = No error
: Even if communication between BusBox and FI is interrupted (e.g. 24V error,
Box removed, etc.), the FI will continue to operate unchanged.
Pos: 318 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P500-P599/Parameter P513 – Telegrammausfallzeit_Ergänzung_02 [SK 511 ... 535E] @ 11\mod_1460111295061_388.docx @ 316490 @ @ 1
NOTE:
SK 511E – SK 535E: If there is communication with an Ethernet module via the
system bus (CANopen), the monitoring time should be at least 0.3 sec. Reason:
When the system bus is active, communication is only carried out as necessary,
however at the latest every 250 ms.
Pos: 319 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P500-P599/Parameter P513 – Telegrammausfallzeit_Ergänzung_01 [SK 1x0E, 2xxE, SK 5xxE] @ 10\mod_1456911365722_388.docx @ 311275 @ @ 1
NOTE:
The process data channels for USS, CAN/CANopen and CANopen Broadcast are
monitoring independently of each other. The decision concerning which channel to
monitor is made by means of the setting in parameters P509 and P510.
For example, in this way it is possible to register the interruption of a CAN Broadcast
communication, although the FI is still communicating with a Master via CAN.
Pos: 320 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P500-P599/Parameter P514 – CAN-Baudrate @ 0\mod_1328092466350_388.docx @ 11203 @ @ 1