05/16/2014 19
NI216
Field Setup or Programming
RV Logic Pin Jumper
This is located on the controller board top. It establishes the voltage at the heat pump (right top terminal block)
RV screw terminal logic to the ODU. Various ODU manufacturers have either a high or low reversing logic
concept. This is a 3-prong arrangement; the 2-position pin jumper will either have the center prong shorted to
the left or to the right.
H/B position – 24 volts for heating (factory default)
C/O position – 24 volts for cooling
Operating Mode
This rotary dial switch determines the various system configurations and must be set by the installer.
Note:
A power-down and power-up reset is required each time the position of this mode switch is changed.
A – heat pump only
B – heat pump with internal boiler boost and backup (factory default)
C – heat pump with external boiler backup
D – not used
Buffer Tank Controller (HP-BTC) Connected
If this is the controlling configuration, pull
J3 pin jumper
at the control board center right.
Note:
The HP-BTC must be set on mode D. This also disables all BTC internal standby (SB), SW
OVER, backup, etc. functions. Also the NorAire Aquastat LED is misleading. Use BTC LED’s to
determine stat control inputs.
Outdoor Temp SW OVER
With mode B or C a boiler backup temperature can be selected (ODT). “Disable” is heat pump only and
“backup” is the full-time boiler. Any measured temperature value less than the set point is boiler only. Factory
default is position 4, 10° F (-12° C).
SW1
OT
Reference
13 SEER
OT
Reference
16 SEER
0 Disable
Disable
Warning
: Some ODU’s have a built-in ODT thermostat
function within their control board. If it is adjustable, set
to disable or less than -10° F (-26° C). Others are fixed.
Example, Electro ODU is fixed at 5° F (-15° C), thus do
not set on position 3 or smaller. Factory default is position
4 (10° F (-12° C)).
1 10 -5
2 15 0
3 20 5
4 25 10
5 25 15
6 25 25
7 Backup
Backup
ĸ
DO NOT USE
PC Setup Download
See next page PC screen for the various factory default conditions and numbers. Contact your Electro Industries
distributor to acquire a software CD with the required USB cable adapter (order ET-SOFT-NA-USB).
The PC CD loaded program has its own HELPS file. This has explanation for all entries and all defaults.
Under pull-down “Communication”, there is a real time temperature monitor selection (Alt-M). This
will give you a separate window with the four temperature values updated approximately every 3
seconds. It can be very helpful when monitoring the NorAire control system. However, when using the
setup screen and attempting a “write” this monitor screen must be closed.
WARNING
AFTER A COMMUNICATION, WRITE, THE NORAIRE CONTROLLER NON-VOLATILE MEMORY IS
CHANGED. IF TROUBLESHOOTING OR CHANGING OF ANY VALUES TO EXPEDITE START-UP OR
TROUBLESHOOTING, THE PREVIOUS OR CORRECT VALUES FOR THE INSTALLATION MUST BE RE-
ENTERED WITH A NEW “WRITE”. TURNING OFF POWER DOES NOT RESTORE FACTORY DEFAULTS.
Utility Interrupt
PC setup determines the action (the “blue” hookup wires are secondary). See Additional Hookup section.
Содержание NC-FE series
Страница 22: ...05 16 2014 20 NI216 ...
Страница 49: ... 0 1 2 3 4 5 6 3 0 1 40 1 5 3 1 7 8 8 4 5 43 15 ...
Страница 50: ... ...
Страница 51: ... ...
Страница 52: ... ...
Страница 53: ... ...
Страница 54: ... ...
Страница 55: ... 01 2 ...
Страница 56: ... 0 0 1 0 2 1 3 4 4 5 0 6 ...
Страница 57: ... ...
Страница 60: ......
Страница 63: ...XX036 ...
Страница 64: ...XX036 ...