Additional Hookup or Special Equipment Concerns
Buffer Tank Controller
Recommended, see various drawing HX103 notes and pages and previous control hookup page.
J3 pin jumper – this must be pulled when the optional Buffer Tank Controller is connected. The internal
micro software must know the buffer tank is now directing all control functions to this NorAire
controller. Also the Buffer Tank Controller mode must be set to
D
.
RV Logic Selection, Control Board Top
The controller must match reversing valve logic of the specific outdoor unit (ODU) connected to this IDU. See
next section – Field Setup.
Utility Interrupt Device, Blue and Blue/Wht Terminal Block
See previous page for connection, but the PC setup download must select the control mode or control load. The
factory default is “ALL” thus a utility load interrupt will drop both compressor and boiler. PC download allows
the option of selecting boiler only.
UTIL INT Tab
External switch to common forces a utility interrupt. This is the same as opening the blue and blue/white
jumper.
Option – COM/NC/NO Tabs
The boiler shutoff valve relay has an auxiliary Form C contact. COM to NO is heating or COM to NC is chilled
water.
Configuration, Forced Air Stat-W (Heating)
Only applies to forced air water coil heating, configuration must be HX103 page 9 or 10 with HP-BTC and N-
3WVK-1. This option 3-way valve kit has installation wiring details. Also see Start Up section.
Mode C, Backup Configuration
Mode B should be used strictly for the internal Electro-Boiler. All external backup should use mode C with the
backup isolated contact (K2). Mode C using gas furnace (not gas boiler connected to the buffer tank) gets very
tricky, the system must be configured with optional Buffer Tank Controller with its mode B (gas furnace)
sequence. K2 is activated in mode C but controlling a gas furnace directly from K2 is
not
recommended. See
hookup drawing NH205 page 2 and HP-BTC installation manual for gas furnace usage during NorAire declared
B/U mode.
Reference mode C, the requirements for external boiler, backup mode:
1. This external boiler shall
not
be piped in series with the NorAire in/out (internal pump).
2. NorAire W-in controls the boiler via K1/K2 isolated contact – bottom left, B
ackup
COM and NO.
3. No other connection to IDU board, including C or 24V.
4. Contains its own safety limits, etc.
5. Contains its own pump or pump relay for its own buffer tank parallel or “side arm” pumping
arrangement.
6. NorAire backup mode is activated from SW OVER setting, Figure 4 sequence, front panel backup
switch, and Hard Hold alarm.
7. If electric boiler, suggest EB-MA-** series and set the target at 120° F (49° C).
a.
Requires independent load control device.
Содержание NC-FE series
Страница 22: ...05 16 2014 20 NI216 ...
Страница 49: ... 0 1 2 3 4 5 6 3 0 1 40 1 5 3 1 7 8 8 4 5 43 15 ...
Страница 50: ... ...
Страница 51: ... ...
Страница 52: ... ...
Страница 53: ... ...
Страница 54: ... ...
Страница 55: ... 01 2 ...
Страница 56: ... 0 0 1 0 2 1 3 4 4 5 0 6 ...
Страница 57: ... ...
Страница 60: ......
Страница 63: ...XX036 ...
Страница 64: ...XX036 ...