background image

52

53

 3.

 

Remove units from the parallel system

There are two methods to remove units from the parallel system:

  First method:

    a)   Touch “CONTROL”

 “Turn off UPS” and select “Yes” to turn of 

the UPS. Then, the UPS will enter into Bypass mode or No Output 

mode without output.

    b)   Turn off the output breaker of this unit, and then turn off the input 

breaker of this unit.

    c)   After it shuts down, you can turn off the battery breaker (for long-

run model) and remove the parallel and share current cables. And 

then remove the unit from the parallel system.

  Second method:

    a)   If the bypass is abnormal, you can not remove the UPS without 

interruption. You must cut off the load and shut down the system first.

    b)   Make sure the bypass setting is enabled in each UPS and then 

turn off the running system. All UPSs will transfer to Bypass mode. 

Remove all the maintenance bypass covers and set the maintenance 

switches from “UPS” to “BPS” position. Turn off all the input 

breakers and battery breakers in parallel system.

    c)   Turn off the output breaker and remove the parallel cable and share 

current cable of the UPS which you want to remove. Now, you can 

remove the UPS from parallel system.

    d)  Turn on the input breaker of the remaining UPS and the system will 

transfer to Bypass mode. Set the maintenance switches from “BPS” 

to “UPS position and put the maintenance bypass covers back on.

    d)  Turn on the remaining UPS according to the previous section.

●  Before turning on the parallel system to activate inverter, make sure 

that all unit’s maintenance switch at the same position.

●  When parallel system is turned on, please do not operate the 

maintenance switch of any unit.

●  Please 

DO NOT

 enable the ECO mode in parallel system.

WARNING (Only for the parallel system)

3.6. Fault Code

Fault code Fault event

Fault code Fault event

01

Bus start failure

43

Overload

02

Bus over

46

Incorrect UPS setting

03

Bus under

47

MCU communication 

failure

04

Bus unbalance

48

Two DSP firmware 

versions are 

incompatible in parallel 

system.

06

Converter over current

60

Bypass phase short 

circuited

11

Inverter soft start failure

61

Bypass SCR short 

circuited

12

High inverter voltage

62

Bypass SCR open 

circuited

15

Inverter B output(line to 

neutral) short circuited

63

Voltage waveform 

abnormal in A phase

16

Inverter C output(line to 

neutral) short circuited

64

Voltage waveform 

abnormal in B phase

17

Inverter A-B output (line 

to line) short circuited

65

Voltage waveform 

abnormal in C phase

18

Inverter B-C output (line 

to line) short circuited

66

Inverter current detect 

abnormal

19

Inverter C-A output (line 

to line) short circuited

67

Bypass O/P short 

circuited

1A

Inverter A negative 

power fault

68

Bypass O/P line to line 

short

circuited

1B

Inverter B negative 

power fault

69

Inverter SCR short 

circuited

1C

Inverter C negative 

power fault

6C

BUS voltage drops too 

fast

21

Battery SCR short 

circuited

6D

Current error value 

detect

23

Inverter relay circuited 

open

6E

SPS power error

Содержание Garun Series

Страница 1: ...OUT UPS UP33TOP110KGAAZ01B UP33TOP115KGAAZ01B UP33TOP120KGAAZ01B UP33TOP130KGAAZ01B UP33TOP140KGAAZ01B UP33TOP160KGAAZ01B UP33TOP180KGAAZ01B Before using this product carefully read all product docum...

Страница 2: ...contents 1 Safetyand EMC instructions 5 1 1 Transportation and storage 5 1 2 Preparation 5 1 3 Installation 5 1 4 Connection warnings 6 1 5 Operation 7 1 6 Standards 7 2 Installation and operation 8...

Страница 3: ...nnect grounding earthing wire to the external UPS battery cabinets or appropriate grounding terminals The UPS can be installed only by qualified maintenance personnel An appropriate disconnect device...

Страница 4: ...arning labels should be placed on all primary power switches installed in places away from the unit to alert the electrical maintenance personnel of the presence of a UPS in the circuit The label will...

Страница 5: ...e they have been designed to provide maximum protection during transportation and storage 2 2 Wiring terminal view 1 RS 232 communication port 2 USB communication port 3 Emergency power off function c...

Страница 6: ...el Diagram 6 Garun 60KL Front view with door open Diagram 4 Garun 40KL Rear panel Diagram 7 Garun 80KL Front view with door open Diagram 8 Garun 60KL 80KL Dual Input Output terminal Diagram 5 Garun 30...

Страница 7: ...and efficiency The cable for Garun 20KL should be able to withstand over 40A current It is recommended to use AWG10 or thicker wire for Phase and AWG 6 or thicker wire for Neutral for safety and effic...

Страница 8: ...the battery pack is correct Pay high attention to the polarity marking on external battery terminal block And make sure the correct battery polarity is connected Wrong connection may cause permanent...

Страница 9: ...PS UPS will enter to power on mode After initialization UPS will enter to No Output mode 3 2 Screen description After initialization the LCD will display main screen There are five sub menus Control m...

Страница 10: ...PS when UPS is off It will show Turn off UPS when UPS is on Touch YES to turn on or off the UPS Then the screen will return to main screen Touch Back to return to main screen immediately or No to canc...

Страница 11: ...r 3 2 3 Measure screen Touch the icon to enter measure page Touch the icon or to browse information Touch the icon to return to main screen Touch the icon to go back to previous menu Measure screen pa...

Страница 12: ...ion of the UPS It s not related to any function parameter ADVANCE It s required to enter password to access to the ADVANCE setting There are two types of authority User and Maintainer SAVE SETTING Thi...

Страница 13: ...f the main screen Mode Mute UPS status mode alarm enable disable If Mode Mute is activated it will show icon on the top right corner of the main screen Advance Advance Password Page It s required to e...

Страница 14: ...t the bypass voltage range L Low voltage point for bypass The setting range is 176V 209V H High voltage point for bypass The setting range is 231V 264V Bypass FREE Range Set the bypass frequency range...

Страница 15: ...fter confirming the pop up screen Restore Delay Min UPS will automatically restart in setting minutes after the UPS shuts down New Password Set up new password to enter ADVANCE User menu Advance Maint...

Страница 16: ...re are twelve options 2A 4A 6A 8A 10A 12A 14A 16A 18A 20A 22A 24A BATT Number The total number of installed battery It should be restart UPS after setting The setting range is 16 20 16 is default sett...

Страница 17: ...tput voltage calibration VOL CALI Page3 Inverter VOL Inverter voltage calibration Bypass VOL Bypass voltage calibration CURR CALI CURR CALI Page Output CURR Output current calibration NOTE Each click...

Страница 18: ...ge INITIAL PARAMETERS page PARAMETERS After pressing the confirmation window it will pop up as shown in above screen Touch YES to restore default value Touch Back or No to cancel this operation and ba...

Страница 19: ...30V and 240V Output Rated FRE Select output rated frequency 50Hz The output frequency is setting for 50Hz 60Hz The output frequency is setting for 60Hz CVCF Mode Constant voltage and constant frequenc...

Страница 20: ...om Rated output voltage 5V to Rated output voltage 11V Rated output voltage 5V is default setting H High voltage point for ECO mode The setting range is from Rated output voltage 5V to Rated output vo...

Страница 21: ...et User password will restore default setting value NO After NO is set the UPS will cancel this operation UPS Selftest UPS Selftest Page This function is only effective when UPS type setting is HV The...

Страница 22: ...set in Basic Setting Basic Information Page2 SYS Install Date The date of system installation BAT Install Date The date of battery installation PAR State The information of parallel state PAR ID The U...

Страница 23: ...ery mode BATT Warning Voltage HIGH High battery warning voltage LOW Low battery warning voltage Shutdown Voltage If battery voltage is lower this point UPS will automatically shut down Battery Age It...

Страница 24: ...Then set the line input breaker at ON position At this time the fan is running and the UPS enter to power on mode for initialization several seconds later UPS operates in Bypass mode and supplies pow...

Страница 25: ...uickly once every sec to remind users that the battery is at low level and the UPS will shut down automatically soon Users could switch off some non critical loads to disable the shutdown alarm and pr...

Страница 26: ...UPS with a multi meter Calibrate the inverter output voltage by configuring inverter voltage adjustment Refer to SETTING VOL CALI screen in LCD menu until the inverter output voltage difference of ea...

Страница 27: ...emaining UPS according to the previous section Before turning on the parallel system to activate inverter make sure that all unit s maintenance switch at the same position When parallel system is turn...

Страница 28: ...re 41 Over temperature 78 LCD MCU communication failed 42 DSP communication failure 3 7 Warning Code Warning code Warning event Warning code Warning event 01 Battery unconnected 21 Line situations are...

Страница 29: ...move excess loads from UPS output and restart it Troubleshooting 4 Problem Possible cause Solutions Fault code is shown as 14 15 16 17 18 or 19 The UPS shut down automatically because short circuit oc...

Страница 30: ...place batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery terminals and the ground is present before maintenanc...

Страница 31: ...ems EU Declaration of Conformity We manufacturer importer declare that the products UPS Garun Series UP33TOP110KGAAZ01B UP33TOP115KGAAZ01B UP33TOP120KGAAZ01B UP33TOP130KGAAZ01B UP33TOP140KGAAZ01B UP33...

Страница 32: ...Memo Memo...

Страница 33: ......

Отзывы: