Battery Parameter:
Battery AH: setting battery capacity.
•
Miscellaneous
Miscellaneous setting page
Auto Restart:
(This function is reserved for future use)
Enable: After “Enable” is set, once UPS shutdown occurs due to low
battery and then utility restores, the UPS will return to line mode.
Disable: After “Disable” is set, once UPS shutdown occurs and the utility
restores, the UPS will not automatically turn on
Shutdown Delay Min:
UPS will shut down in setting minutes. The countdown
will start after confirming the pop-up screen.
Restore Delay Min:
UPS will automatically restart in setting minutes after the
UPS shuts down.
New Password:
Set up new password to enter “ADVANCE
►
User” menu.
Advance - Maintainer
Advance: Maintainer Setting Menu Page1
Advance: Maintainer Setting Menu Page2
To access the “Advance-Maintainer” Setting menu page, it’s required to enter
password. Please contact your local dealer to get maintainer password.
NOTE!
This setting menu is only for qualified technician. Otherwise, mis-operation will
cause UPS damage.
There are nine sub-menus under “Advance
►
Maintainer” setting: SYS
PARAMETER, INSTALL INFO, VOL CALI, CURR CALI, INITIAL, ELECTRONIC,
BATT, MISCELLANEOUS and UPS SELFTEST.