INITIAL EEPROM page
EEPROM:
After pressing the confirmation window, it will pop up as shown in
above screen. Touch “YES” to clear all setting value in EEPROM. Touch “Back”
or “No” to cancel this operation and back to INITIAL menu page.
INITIAL TOUCH page
TOUCH CALI:
After pressing the confirmation window, it will pop up as
shown in above screen. Touch screen to recalibrate. Then, the blue screen
appears and please touch the place where white cross is located.
•
ELECTRONIC
Electronic Setting page 1
Output Voltage:
Select the output rated voltage. There are four options:
208V, 220V, 230V and 240V.
Output Rated FRE:
Select output rated frequency.
50Hz: The output frequency is setting for 50Hz.
60Hz: The output frequency is setting for 60Hz.
CVCF Mode:
Constant voltage and constant frequency function.
Enable: CVCF function is enabled. The output frequency will be fixed at
50Hz or 60Hz according to setting of “Output Freq.”. The input frequency
could be from 46Hz to 64Hz.
Disable: CVCF function is disabled. The output frequency will synchronize
with the bypass frequency within 46~54 Hz for 50Hz system or within
54~64 Hz for 60Hz system. Disable is the default setting.
Bypass Forbid:
Enable: Bypass Forbid is enabled. It’s not allowed for running in Bypass
mode under any situations.
Disable: Bypass Forbid is disabled. UPS will run in Bypass mode. It is the
default setting.