3.2.6. Data Log screen

Touch the icon 

 to enter data log page. Data log is used to record the 

warning and fault information of the UPS. The record contains date & time, 

code, type and description. Touch the icon 

 or 

 to browse information. 

Touch the icon 

 to return to main screen. Touch the icon 

 to go back to 

previous menu.

Please refer to Section 3-6 and 3-7 for warning and fault code list.

Data log page

3.3. Audible alarm

Description

Buzzer status

Muted

UPS status

Bypass mode

Beeping once every 2 minutes

Yes

Battery mode

Beeping once every 4 seconds

Fault mode

Beeping continuously

Warning

Overload

Beeping twice every second

No

Others

Beeping once every second

Fault

All

Beeping continuously

Yes

3.4. Single UPS operation

 1.

 

Turn on the UPS with utility power (in AC mode)

  After power supply is connected correctly, set the breaker of the battery 

pack at “ON” position (this step only necessary for long-run model). Then set 

the line input breaker at “ON” position. At this time the fan is running and 

the UPS enter to power on mode for initialization, several seconds later, UPS 

operates in Bypass mode and supplies power to the load via the bypass.

NOTE! 

When UPS is in Bypass mode, the output voltage will directly power from utility 

after you switch on the input breaker. In Bypass mode, the load is not protected 

by the UPS. To protect your precious devices, you should turn on the UPS. 

  Touch “CONTROL” and select “UPS on/off” icon. It will show “Turn on 

UPS?” in screen and select “Yes”. Refer to On/Off UPS screen.

  A few seconds later, the UPS will enter into AC mode. If the utility is 

abnormal, the UPS will operate in Battery mode without interruption.

NOTE! 

When the UPS running out battery, it will shut down automatically at Battery 

mode. When the utility is restored, the UPS will auto restart in AC mode.

  2.  Turn on the UPS without utility power supply (in Battery mode)

  Make sure that the two strings of batteries are connected correctly at 

UPS’s ”+,GND,-” terminals and the breaker of the battery pack is at “ON” 

position (only for long-run model).

Содержание Garun Series

Страница 1: ...OUT UPS UP33TOP110KGAAZ01B UP33TOP115KGAAZ01B UP33TOP120KGAAZ01B UP33TOP130KGAAZ01B UP33TOP140KGAAZ01B UP33TOP160KGAAZ01B UP33TOP180KGAAZ01B Before using this product carefully read all product docum...

Страница 2: ...contents 1 Safetyand EMC instructions 5 1 1 Transportation and storage 5 1 2 Preparation 5 1 3 Installation 5 1 4 Connection warnings 6 1 5 Operation 7 1 6 Standards 7 2 Installation and operation 8...

Страница 3: ...nnect grounding earthing wire to the external UPS battery cabinets or appropriate grounding terminals The UPS can be installed only by qualified maintenance personnel An appropriate disconnect device...

Страница 4: ...arning labels should be placed on all primary power switches installed in places away from the unit to alert the electrical maintenance personnel of the presence of a UPS in the circuit The label will...

Страница 5: ...e they have been designed to provide maximum protection during transportation and storage 2 2 Wiring terminal view 1 RS 232 communication port 2 USB communication port 3 Emergency power off function c...

Страница 6: ...el Diagram 6 Garun 60KL Front view with door open Diagram 4 Garun 40KL Rear panel Diagram 7 Garun 80KL Front view with door open Diagram 8 Garun 60KL 80KL Dual Input Output terminal Diagram 5 Garun 30...

Страница 7: ...and efficiency The cable for Garun 20KL should be able to withstand over 40A current It is recommended to use AWG10 or thicker wire for Phase and AWG 6 or thicker wire for Neutral for safety and effic...

Страница 8: ...the battery pack is correct Pay high attention to the polarity marking on external battery terminal block And make sure the correct battery polarity is connected Wrong connection may cause permanent...

Страница 9: ...PS UPS will enter to power on mode After initialization UPS will enter to No Output mode 3 2 Screen description After initialization the LCD will display main screen There are five sub menus Control m...

Страница 10: ...PS when UPS is off It will show Turn off UPS when UPS is on Touch YES to turn on or off the UPS Then the screen will return to main screen Touch Back to return to main screen immediately or No to canc...

Страница 11: ...r 3 2 3 Measure screen Touch the icon to enter measure page Touch the icon or to browse information Touch the icon to return to main screen Touch the icon to go back to previous menu Measure screen pa...

Страница 12: ...ion of the UPS It s not related to any function parameter ADVANCE It s required to enter password to access to the ADVANCE setting There are two types of authority User and Maintainer SAVE SETTING Thi...

Страница 13: ...f the main screen Mode Mute UPS status mode alarm enable disable If Mode Mute is activated it will show icon on the top right corner of the main screen Advance Advance Password Page It s required to e...

Страница 14: ...t the bypass voltage range L Low voltage point for bypass The setting range is 176V 209V H High voltage point for bypass The setting range is 231V 264V Bypass FREE Range Set the bypass frequency range...

Страница 15: ...fter confirming the pop up screen Restore Delay Min UPS will automatically restart in setting minutes after the UPS shuts down New Password Set up new password to enter ADVANCE User menu Advance Maint...

Страница 16: ...re are twelve options 2A 4A 6A 8A 10A 12A 14A 16A 18A 20A 22A 24A BATT Number The total number of installed battery It should be restart UPS after setting The setting range is 16 20 16 is default sett...

Страница 17: ...tput voltage calibration VOL CALI Page3 Inverter VOL Inverter voltage calibration Bypass VOL Bypass voltage calibration CURR CALI CURR CALI Page Output CURR Output current calibration NOTE Each click...

Страница 18: ...ge INITIAL PARAMETERS page PARAMETERS After pressing the confirmation window it will pop up as shown in above screen Touch YES to restore default value Touch Back or No to cancel this operation and ba...

Страница 19: ...30V and 240V Output Rated FRE Select output rated frequency 50Hz The output frequency is setting for 50Hz 60Hz The output frequency is setting for 60Hz CVCF Mode Constant voltage and constant frequenc...

Страница 20: ...om Rated output voltage 5V to Rated output voltage 11V Rated output voltage 5V is default setting H High voltage point for ECO mode The setting range is from Rated output voltage 5V to Rated output vo...

Страница 21: ...et User password will restore default setting value NO After NO is set the UPS will cancel this operation UPS Selftest UPS Selftest Page This function is only effective when UPS type setting is HV The...

Страница 22: ...set in Basic Setting Basic Information Page2 SYS Install Date The date of system installation BAT Install Date The date of battery installation PAR State The information of parallel state PAR ID The U...

Страница 23: ...ery mode BATT Warning Voltage HIGH High battery warning voltage LOW Low battery warning voltage Shutdown Voltage If battery voltage is lower this point UPS will automatically shut down Battery Age It...

Страница 24: ...Then set the line input breaker at ON position At this time the fan is running and the UPS enter to power on mode for initialization several seconds later UPS operates in Bypass mode and supplies pow...

Страница 25: ...uickly once every sec to remind users that the battery is at low level and the UPS will shut down automatically soon Users could switch off some non critical loads to disable the shutdown alarm and pr...

Страница 26: ...UPS with a multi meter Calibrate the inverter output voltage by configuring inverter voltage adjustment Refer to SETTING VOL CALI screen in LCD menu until the inverter output voltage difference of ea...

Страница 27: ...emaining UPS according to the previous section Before turning on the parallel system to activate inverter make sure that all unit s maintenance switch at the same position When parallel system is turn...

Страница 28: ...re 41 Over temperature 78 LCD MCU communication failed 42 DSP communication failure 3 7 Warning Code Warning code Warning event Warning code Warning event 01 Battery unconnected 21 Line situations are...

Страница 29: ...move excess loads from UPS output and restart it Troubleshooting 4 Problem Possible cause Solutions Fault code is shown as 14 15 16 17 18 or 19 The UPS shut down automatically because short circuit oc...

Страница 30: ...place batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery terminals and the ground is present before maintenanc...

Страница 31: ...ems EU Declaration of Conformity We manufacturer importer declare that the products UPS Garun Series UP33TOP110KGAAZ01B UP33TOP115KGAAZ01B UP33TOP120KGAAZ01B UP33TOP130KGAAZ01B UP33TOP140KGAAZ01B UP33...

Страница 32: ...Memo Memo...

Страница 33: ......

Отзывы: