pmg511en21p01 37
5.10.6.2 Digital Input Button Setting
[PAR5 → DI-K]
To use the digital input button function, all functions must be first be assigned to the buttons. Default setting:
STOP.
Setting
Description
STOP
RUN / STOP
AlRE
Deactivate forced alarm output
AT
Automatic tuning RUN / OFF (for PID control)
OFF
Not used
Note: If the digital input button and the digital input terminal are set the same, the digital input button will not work.
To use the digital input button:
In ″Normal″ mode, press and hold the
+
buttons for 3 seconds to perform the assigned function
(deac-
tivate run / stop or alarm output)
.
Note: If the same function is assigned to the digital input button and the digital input terminal, it is activated as an ″or″
function and deactivated as an „and” function. (However, this does not apply to the Multi SV function [MtSV] of the digital
input terminals.) The digital input button functions work regardless of the password settings [PAR5 → PWD].
5.10.7 User Level Settings
[PAR5 → USER]
Displaying the parameters can be restricted by setting the user level
(normal or high)
.If set to standard user, only
the main function parameters shaded in the complete parameter list are only displayed. Default setting: STND.
Settings
Description
STND
Activates standard user parameters
HIGH
Activates all parameters
5.10.8 SV Group Lock
[PAR5 → LcSV]
The modification of
SV
parameters can be restricted by locking the
SV
group parameters, which include
SV
selection, digital input button
(
buttons for 3 seconds)
,
button for monitoring and manual control,
parameter reset
[INIT]
, and so on. Default setting: OFF.
Setting
Function
ON
Activates the SV group lock.
OFF
Disables the SV group lock.
5.10.9 Parameter Group Lock
[PAR5 → LcP1/LcP2/LcP3/LcP4/LcP5]
Lock or unlock each parameter group from parameter group 1
[PAR1]
to parameter group 5
[PAR5]
.
The parameter settings can be read even if the parameter group lock is set.
For parameter 5
[PAR5]
, the settings can be changed even if the
[LcSV
/ LcP □]
lock is initialized.
Default setting: OFF.
Parameter
Description
ON
Lock parameter group
OFF
Unlock parameter group
5.10.10 Reset Parameter
[INIT]
This function resets all parameters in the memory to the factory defaults.
Press and hold the
buttons on the front panel front panel for 5 seconds. The
[INIT]
parameter is
displayed. Select ″YES″ to reset the parameters. Default setting: NO.
Note: If the password function is enabled, a password must be entered to activate the function. Resetting the parameters
also resets the password.