pmg511en21p01 35
5.9.6 Enable / Disable Communication Writing
[PAR4→ COMW]
This function can change the parameter settings stored in the memory with the PC, GP, PLC, etc. to enable or
disable writing. Default setting: EnA.
Setting
Description
EnA
Enable parameter set / modification via communication.
DIsA
Prohibit the setting or modification of parameters by communication.
Note: Parameter settings can be read even if writing them is disabled.
5.10 OTHER FUNCTIONS
5.10.1 Heating MV Monitoring
Displays the current heating
MV
during heating control or heating and cooling control. The
MV
can be set
manually to control the temperature.
Measuring range:
H 0.0…H 100
(unit: %)
Note: The MV can be displayed with a moving decimal point (H99.9 → H100).
5.10.2 Cooling MV Monitoring
Displays the current cooling
MV
during cooling control or heating and cooling control. The
MV
can be set
manually for temperature control.
Measuring range:
C 0.0…C 100
(unit: %)
Note: The MV can be displayed with a moving decimal point (C99.9 → C100).
5.10.3 Heating Current Monitoring
[PAR1 → CT-A]
This function monitors and displays the current of the controlled heater
(load)
. Unit: A.
Note: A current transformer (CT) is used to measure and display the heating (load) current. The availability of the heating
current monitoring function varies by model and controller output type. For the heater-cooler model, the heater flow
monitor function can be used on OUT1.
5.10.4 RUN/STOP
[PAR1 → R-S]
In ‘Normal’ mode
(RUN)
, users can manually start or stop control output. Default setting: RUN.
The stop command stops the control output. However, the auxiliary output is not affected by this command.
This function can be enabled by configuring the parameters. In addition, the digital input buttons on the front
panel
(for
3 seconds)
and the digital input terminals
(DI-1)
can be assigned to the
[STOP]
function.
Setting
Description
RUN
Forced control output start in STOP mode.
STOP
Forced control output stop in ‘Normal’ mode.
Note: When the stop function is enabled, the front panel SV display will show STOP. The setting can be changed when
the controller stopped. The stop status remains in effect even after the controller is stopped and turned on again. When
the STOP mode is active, STOP MV [StMV] is present at the output. If a sensor is interrupted in STOP mode, the STOP
MV [StMV] is displayed. The run / stop setting remains in effect even after the power is turned back on. If the digital input
(DI-1) function is set to RUN / STOP [STOP], the RUN / STOP function is not possible to change by the front buttons or
parameters.
5.10.4.1 Stop Control Output Settings
[PAR5 → StMV]
This parameter sets the output value of the controller when stopped. Use the ON / OFF control to select between
100
(ON)
and 0.0
(OFF)
. With PID control, the user can set the
MV
value between 0.0 and 100.
Default setting: 0.0%.