pmg511en21p01 27
– Condition of standby sequence 2, alarm latch and repeated standby mode of standby sequence 2 again:
switch on, change set temperature, alarm temperature
[AL1]
or alarm operation
[AL-1]
, switch STOP mode
to
″Normal″
mode.
Note: If the alarm operation is set to loop break alarm [LBA], sensor fault alarm [SBA] or heating fault alarm [HBA], only
the standard alarm [AL-A] and alarm interlock [AL-C] will be displayed.
5.7.3 Alarm Output Lower
[PAR1 → AL1L]
and Upper
[PAR1 → AL1H]
Limit Value Settings
Output alarm activation values can be set. The
[AL1H / AL1L]
configuration parameters are activated for each
setting according to the selected alarm operation. The upper / lower limit values are according to the individual
input specification of the sensor. The lower limit is the reference value for determining burnout of the heating
element.
Default setting - Temperature: 1550 / Analog: 100.0
Note: Changing the alarm action or options will reset the settings to the highest or lowest values that will not trigger output
in the new mode.
5.7.4 Alarm Output Hysteresis
[PAR4 → A1HY]
Setting the on / off interval for alarm output 1
(5.7.1 Alarm operation
[PAR4 → AL-1]
)
.
″H″
means the hysteresis
of the alarm output in alarm operation. It is used to set the interval between the ON / OFF periods of the alarm
outputs.
Default setting: 1. It is set to °C / °F / %.
Note: Alarm Output Hysteresis applies the same to Heating error alarm [HBA]. This parameter is not displayed when Loop
Break Alarm [LBA] or Sensor Fault Alarm [SBA] is selected.
5.7.5 Alarm NO/NC
[PAR4 → A1N]
Selects the contact type for alarm output 1. The contact mode of the relay can be set in the event of an alarm.
Default setting: NO.
Setting
Decription
NO
Normally open – Stays open normally and closes when there is an alarm.
NC
Normally closed – Stays closed normally, opens only when there is an alarm.
Front LED Indicators
Change
Alarm trigger
Alarm output
Front LED
NO
(normally open)
OFF
Open
□
OFF
ON
Close
■ ON
NC
(normally closed)
OFF
Close
□
OFF
ON
Open
■ ON
5.7.6 Alarm Output Delay Settings
[PAR4 → A1ON / A1OF]
The alarm output delay can be set to prevent false alarms caused by faulty input signals due to interference or
noise. The default setting for both parameters: 0 s.
If there is a preset delay time, the alarm output will not turn on for the preset time. Instead, the front alarm indicator
flashes every 0.5 seconds.