Box Message
Explanation
32
HART:Too large
The received HART command is longer than standard
33
HART:Too small
The received HART command is shorter than standard
34 HART:Few
data
35
HART:Device spec.
Bad parameter sent during remote programming
36 HART:Access
restr.
37 HART:Busy
38
HART:Comm. not. imp.
The received HART command is unknown to the MultiCONT
39
Please wait!
DEV detect cannot run due to periodic disturbance on the HART line, which causes continuous error!
40
TOT cleared
TOT deleted during relay progamming ( Impulse F )
41
TOT updated
TOT updated during relay progamming ( Impulse F )
42
No in RP mode
Device could not enter „Remote programming” (RP) mode during programming
43
Stick in RP mode
Unsuccessful exit after remote programming of device
9.2.
O
THER
M
ESSAGES
:
No.
Message
Explanation
1
Scanning HART line
Displayed during device detection
2 Logical
error
-
Displayed instead of user’s image, if
difference
or
average
is selected, but there is only one active device
-
Displayed if the dimensions of the results of the selected devices are different
3
No user screen
In „Main menu”/”MultiCONT config.”/”User display” „None” is selected
4 No
active
device Displayed during measurement or instead of user’s image, when there is no avtive device
5
No HART device
The unit’s device list is empty ( run „DEV detect”
6
Locked
The hardware switch is on ( the program cannot be modified)
7
No current output
Displayed in the position of the „current output assignment” image, if there is no current output in the system
8
No relay output
Displayed in the position of the „Relay assignment” image, if there is no relay in the system