In the above example, current output C1_IN is controlled by the difference between the secondary values of SE300 and SP380. In the case of a single unit, the sign is
indifferent; in fact, average might as well be selected. In the case of the selection of multiple devices, functioning depends on the result of the mathematical sum. If in
the case of selected multiple devices the dimensions or the values are different, the unit will display an error message. Upon selecting the value, confirm that the
appropriate HART command has been seleceted for the device (See Main menu/MultiCONT config/HART / command set, see chapter 5.4.5.5)
5.8.3.2
Function
28
Curr. out.: C1_IN
Program
Short TAG
Info
Program
Source
Function
Parameter
Test
Variable
Error 3.6 mA
Error 22 mA
Variable H
Variable H
= 3.6mA
= 22mA
Function
31
Not selected
Selected
Select using
F
UNCTION
D
ESCRIPTION OF
O
PERATION
P
ROG
.P
AR
.
Variable
Operates in accordance to the selected (PV, SV, TV, QV) value in the “Source” menu point.
The value in CP1 parameter is assigned to 4mA, the value in CP2 parameter is assigned to 20mA.
CP1
CP2
Error 3.6mA
Error 22mA
CP3=0 in every cases it is the error current
CP3=n in case of “n” coded error it is the error current
Error codes (see chapter 6)
If there is no error, value of the current output is 4mA
CP3
Variable H = 3.6mA
Variable H = 22mA
The previous two functions in one:
Until there is no error, it works according to the selected (PV, SV, TV, QV) value in the “Source” menu
point.
The value in CP1 parameter is assigned to 4mA, the value in CP2 parameter is assigned to 20mA.
In case of any error, selected error current will be applied.
CP1
CP2
CP3