This procedure is repeated in every turning ON/OFF and restart.
Then the measurement data are sent continuously to the LOGGER unit (flashing green LED indicates) and in case of fulfilment of the selected conditions
(see chapter 5.4.8.1) they are logged, which is indicated by the flashing red LED.
Capacity of the on-board FLASH memory is 65000 entries. When this memory is became full and there is no SD card in the card-reader, the old entries will be
overwritten so the logging will be performed by a “rotation”. Number of overflows can be read out in the “LOG”/”Info” menu point. When there is an SD card in the slot
the read and write process is done with the frequency selected in “LOG”/”Settings”/SD saving mode” menu point. Maximal capacity of the SD card is 2 GB. One entry
is about 200 byte, so this capacity provides storing entries more than a million.
The LOGGER unit of the MultiCONT senses automatically the inserted SD card. Then saving the FLASH memory into the memory card commences automatically.
State of this process can be followed in the trend bargraph. Before remove the memory card, the end of the write process (when the red LED does not flash) has to
be waited. In order to avoid removing the card during the write process, push the ESC and the
↑
buttons at the same time. Then the following box message will be
shown on the display:
From this moment the MultiCONT does not send any data for 10 seconds to the LOGGER unit (write is unavailable) and the
SD card can be safely removed.
SD card
can be removed
Everything is OK
Red and green LED-s are flashing until
this caption appears
LOGGER card is not working properly
In this case
P-200 :LOG IP
entry will be
created in the error-list
LOGGER PRESENT
LOGGER NOT PRESENT