Window (window comparator)
Default: Invert= OFF
Between RP1 and RP2 relay will be energized
Inverted operation (Between RP1 and RP2 relay will be de-
energized)
or by selecting Invert = ON
RP1
RP2
t
Energised
De-energised
Relay
RP1,
RP2
Window D (comparator with delayed switching)
Default: Invert = OFF
Between RP1and RP2 relay will be energized using delay in
RP3 (Factory default t= 0 sec )
Inverted operation (Between RP1and RP2 relay will be de-
energized )
or by selecting Invert = ON
RP1
RP2
t
Energised
Delay
K
De-energised
Relay
K
K
K
K
RP1,
RP2,
RP3
Error
Default: Invert = OFF
In case of error relay will be de-energized. RP3=0 for any error; RP3=n for error of code
n
Inverted operation (in case of error relay will be energized ) or by selecting Invert =ON
RP3
Impulse F
Default: Invert = OFF
relay will be energized for appr. 200ms for each unit volume
set in
RP3
Operation
can be
inverted by selecting Invert = ON
Programming error will be displayed if:
more than one device (transmitter) is marked as source
RP3 = 0
t
De-energised
Relay
TOT1
20
10
Energised
RP3=10
RP3