199
10e
CHARGER
Power voltage (V)
Voltage tap
199 or lower
200V
200 - 209
210V
210 - 219
220V
Power voltage (V)
Voltage tap
379 or lower
380V
380 - 399
400V
400 - 419
420V
420 - 439
440V
461E116
Body side
Transformer side
Isolation tubes
are placed on for
unused taps.
Voltage and frequency
are marked on each wire.
<Input voltage: 200V>
<Input voltage: 400V>
Voltage tap
10e- 5.
3-core cable
(VCT)
Isolation tube
Washer
Nut
These wires must be
connected securely with
bolt and nut.
Primary coil
Secondary
coil
Voltage taps connection position
2210221E
l
Location of the voltage tap
10e-5-1. Power supply voltage - check
CAUTION
l
The measurement should be made when the peripheral facilities are
not used, such as during the lunch time or at night.
NOTE
l
Measure the power supply voltage at the charging section without
running the charger.
l
Measure the voltage for 1 minute. The highest voltage obtained is the
power voltage.
l
If three-phase input power is used, the average of the highest voltages
of each phase (U-V, U-W, and V-W) is the power supply voltage.
10e-5-2. Voltage tap - selection
l
Select a tap to match with the power supply voltage at
the charging place.