31
GENERAL EMC - HARMONICS - MAINS INTERFERENCE
Powerdrive MD2S Installation guide
4972 en - 2017.08 / d
4.6 - Electromagnetic compatibility (EMC)
CAUTION:
Conformity of the drive is only assured when the mechanical and electrical installation instructions described in this
manual are adhered to.
Immunity
Standard
Description
Application
Conformity
IEC 61000-4-2
Electrostatic discharges
Product casing
Level 3 (industrial)
EN 61000-4-2
IEC 61000-4-3 Immunity standards for radiated
radio-frequency
Product casing
Level 3 (industrial)
EN 61000-4-3
IEC 61000-4-4
Bursts of fast transients
Control cable
Level 4 (industrially hardened)
EN 61000-4-4
Power cable
Level 3 (industrial)
IEC 61000-4-5
Shock waves
Power cables
Level 4
EN 61000-4-5
IEC 61000-4-6 Generic immunity standards for
conducted radio-frequency
Control and power
cables
Level 3 (industrial)
EN 61000-4-6
EN 50082-2
Generic immunity standards for
the industrial environment
-
Conforming
IEC 61000-6-2
EN 61000-6-2
EN 61800-3
Variable speed drive standards
Conforming to the first and second environment
IEC 61800-3
EN 61000-3
Emission
Standard
Description
Catégory
Conformity conditions
Standard
With optional RFI filter
EN 61800-3
Variable speed drive standards
C1
-
-
C2
-
Conforming
- Cable length < 10 m
- Switching frequency < 4 kHz
C3
Conforming
- Cable length < 100 m
- Switching frequency < 4 kHz
Conforming
- Cable length < 100 m
- Switching frequency < 6 kHz