MECHANICAL INSTALLATION
Powerdrive MD2S Installation guide
4972 en - 2017.08 / d
L= 4x 400 mm
or 4x 600 mm
L= 3x 400 mm
or 3x 600 mm
L = 2x 400 mm
or 2x 600 mm
or 2x 600 + 400 mm
L = 400 mm
or 600 mm
or 600 + 400 mm
2 - MECHANICAL INSTALLATION
• It is the responsibility of the owner or user of the
Powerdrive MD2S to ensure that installation,
operation and maintenance of the drive and its options
comply with legislation relating to the safety of
equipment and personnel, and with the current
regulations in the country of use.
• The Powerdrive MD2S drives must be installed in
an environment free from conducting dust, corrosive
fumes, gases and fluids, and condensation (class 2
according to IEC 664-1). The Powerdrive MD2S must not
be installed near flammable materials. The drives must
not be installed in hazardous areas unless they are in
appropriate enclosures. In this case, the installation
must be approved.• In atmospheres where condensation
can form, install a heating system (to be switched off
when the drive is operating).
• Prevent access by unauthorized personnel.
2.1 - Checks on receipt
Make sure that the drive cabinet has been
transported vertically, otherwise it could be
damaged.
Before installing the
Powerdrive MD2S,
check that:
- The drive has not been damaged during transport
- The information on the nameplate is compatible with the
power supply
2.2 - Handling
• The center of gravity could be high up
and/or off-centre, so beware of the risk of the drive
cabinet tipping over.
• Check that the handling equipment is suitable for the
weight to be handled.
• The lifting accessories provided are limited solely
to handling the drive cabinet. If subsequent handling
operations are carried out, always check that these lifting
accessories are in good condition.
The drive cabinet must be handled without the IP21 or IP54
roof in place.
The
Powerdrive MD2S
IP21 versions are supplied with the
roof assembled. Before handling the drive cabinet, follow the
procedure described in section2.4. For handling, follow the
instructions below, and then re-fit the roof.
The
Powerdrive MD2S
IP54 versions are supplied with the
lifting rings or rails fitted. When handling the drive cabinet,
follow the instructions below, depending on the cubicle width,
as indicated below. After handling, assemble the roof as
described in section 2.5.
Above 2,400 mm wide (W), a baseplate 100 mm high is
installed as standard to ensure the rigidity of all the drive
cabinets.