Note:+50%F.S. is set prior to delivery.

An example of setting 6MPa for switch output 1(SW1 LED is flashing)with 104R.

To set switch output 1 the SW1 LED should be flashing. (To set switch output 2 the SW2 LED should be flashing.)

Note:20counts is set prior to delivery.

An example of setting a hysteresis value of 0.8MPa with the 104R(MPa).

To set hysteresis the“−”LED should be flashing. 

To set Digital Filter all LED should be not flashing. An example of setting 2.5s response time by Digital Filter.

Note:“F-0”is set prior to delivery.

+/−

SW1

SW2

+/−

SW1

SW2

M P a

+/−

SW1

SW2

C O PA L     E L E C T R O N I C S

H

M P a

+/−

SW1

SW2

C O PA L     E L E C T R O N I C S

H

M P a

+/−

SW1

SW2

C O PA L     E L E C T R O N I C S

H

M P a

+/−

SW1

SW2

C O PA L     E L E C T R O N I C S

H

The LED of an item flashes 

when selected using the     button.

Hysteresis setting

Switch output 2

setting

Switch output 1

setting

F-0:Response Time=5ms

F-1:Response Time=25ms

F-2:Response Time=250ms

F-3:Response Time=2.5s

Press the   and   buttons

 

simultaneously to enter the 

Pressure Settings Mode. 

(The SW1 LED flashes.)

Press the   button to select 

between switch output 1 setting

(SW1), switch output 2 setting

(SW2), or the hysteresis setting.

Set the value using the

  and   buttons.

Press the   button for more 

than one second to return to 

the Operations Mode.

Digital filter setting

Press the  and  buttons.

Press the  button until 

all LED do not flashe.

Set the value to “F-3”

using the  and  

buttons.

Press the  button for 

more than one second to 

return to the Operations 

Mode.

Press the     button until 

the SW1 LED flashes.

Set the value to “6.00”

using the  and   

buttons.

Press the  and  buttons.

Press the  button until 

the −LED flashes.

Set the value to “0.80”

using the  and  

buttons.

Press the  button for 

more than one second to 

return to the Operations 

Mode.

Press the  button for 

more than one second to 

return to the Operations 

Mode.

Press the  and  buttons 

6

Switch Output Setting

Hysteresis setting

Digital Filter setting

Pressure Settings Mode

Содержание PG-35H 104R

Страница 1: ...ater Such as oil solvent and etc and outdoor Do not use pointed objects such as pens to press the setting buttons on the display panel as this may push holes in the setting buttons and damage them Do...

Страница 2: ...o outputs NPN PNP Transistor open collector Switch rating 30VDC100mA maximum Residual voltage 1 2V maximum NPN 2 2V maximum PNP at 100mA Display Operation display Operating conditions Thermal error Fi...

Страница 3: ...itial Settings Mode Setting1 Setting2 Hysteresis 0 300 counts Digital Filter F 0 F 3 Press the and buttons simultaneously Press the button more than one second Press the button more than one second Pr...

Страница 4: ...9 A b 1 0 99 9 1 0 99 9 0 01 1 45 0 10 9 99 1 357 1 350 0 01 5 07 0 1 35 0 0 0102 0 01 145 0 001 Value selected Pressure range Pr Pr Muitiplier factor 104R 354R Set the value of the third digit to 2...

Страница 5: ...F OFF SW1 SW2 Setting value 1 Setting value 2 Hysteresis Hysteresis Low High There are four operation modes These are shown in the diagrams below Value selected Output Mode Operation 1 2 3 4 5 6 7 8 S...

Страница 6: ...25ms F 2 Response Time 250ms F 3 Response Time 2 5s Press the and buttons simultaneously to enter the Pressure Settings Mode The SW1 LED ashes Press the button to select between switch output 1 setti...

Страница 7: ...he applied pressure to the atmospheric pressure and try zero point adjustment again Turn o the power and verify the load connected switch output 1 and 2 E 1 E 2 999Flashing Pressure values exceed the...

Страница 8: ...nd Non Display Temporary Mode will be set After 10 seconds display will go o To disable Non Display Temporary Mode press key for more than 4 seconds will be displayed and Non Display Temporary Mode wi...

Страница 9: ...ng part R2 type 9 Outline Dimensions Unit mm 31 4 COPAL ELECTRONICS 73 2 kPa R1 4 Fe Ni COPAL ELECTRONICS 31 4 kPa 79 2 G3 8 SUS316L 16 10 5 37 Five core shielded cable L 2000 100 Depth5 16 32 Five co...

Страница 10: ...f gauge sides Description Appllcable model Panel holder cover panel holder PG 30 35 PG 35H Holder cover set Main body Panel holder Panel holder cover 24 7 5 7 4 5 40 42 6 COPAL ELECTRONICS kPa 10 Brac...

Отзывы: