An example of setting “2”.

※Change of magnification setting is effective only for pressure reading. Set values for switching are not scaled automatically.

The multiplier factor setting is determined by the value of the third digit : the red −LED should be 

flashing during the setting.

The analog output setting is determined by the value of the second digit:the green SW1 LED should 

be flashing during the setting.

Sections containing an oblique stroke are multiplier factor that cannot be selected because of resolving power or display digits.

 (Values will not be displayed automatically.)

Note:“A” is set prior to delivery.      

An example of setting the R mode in the 104R range.

Note:G mode are set prior to shipment.

1
2
3
4
5
6
7
8
9

A

b

−1.0〜99.9

−1.0〜99.9

−0.01〜1.45
−0.10〜9.99

−1〜357

−1〜350

−0.01〜5.07

−0.1〜35.0

×0.0102

×0.01

×145
×0.001

Value selected

Pressure range(−Pr〜+Pr)

Muitiplier factor

104R

354R

Set the value of the third

digit to “2” using    and

  buttons.

In the operations mode, press

the  and  buttons simultaneously

to enter the Initial Settings Mode.

Press the   button until

the − LED under the

third digit flashes.

Press the  button for more

than one second to return

to the Operations Mode.

Value selected

1
2

R mode(Compound pressure output)
G mode(Positive pressure output)

Mode

−Pr           0           +Pr

(Vzero)

1V

1V

5V
5V

In the Operations Mode, press the
  and  buttons simultaneously to
enter the Initial Settings Mode.

Press the  button until the
SW1 LED under the second
digit flashes.

Set the value of the second
digit to “1” using the  and
  buttons.

Press the  button for more 
than one second to return to 
the Operations Mode.

4

Multiplier factor Setting

Analog Output Setting

Содержание PG-35H 104R

Страница 1: ...ater Such as oil solvent and etc and outdoor Do not use pointed objects such as pens to press the setting buttons on the display panel as this may push holes in the setting buttons and damage them Do...

Страница 2: ...o outputs NPN PNP Transistor open collector Switch rating 30VDC100mA maximum Residual voltage 1 2V maximum NPN 2 2V maximum PNP at 100mA Display Operation display Operating conditions Thermal error Fi...

Страница 3: ...itial Settings Mode Setting1 Setting2 Hysteresis 0 300 counts Digital Filter F 0 F 3 Press the and buttons simultaneously Press the button more than one second Press the button more than one second Pr...

Страница 4: ...9 A b 1 0 99 9 1 0 99 9 0 01 1 45 0 10 9 99 1 357 1 350 0 01 5 07 0 1 35 0 0 0102 0 01 145 0 001 Value selected Pressure range Pr Pr Muitiplier factor 104R 354R Set the value of the third digit to 2...

Страница 5: ...F OFF SW1 SW2 Setting value 1 Setting value 2 Hysteresis Hysteresis Low High There are four operation modes These are shown in the diagrams below Value selected Output Mode Operation 1 2 3 4 5 6 7 8 S...

Страница 6: ...25ms F 2 Response Time 250ms F 3 Response Time 2 5s Press the and buttons simultaneously to enter the Pressure Settings Mode The SW1 LED ashes Press the button to select between switch output 1 setti...

Страница 7: ...he applied pressure to the atmospheric pressure and try zero point adjustment again Turn o the power and verify the load connected switch output 1 and 2 E 1 E 2 999Flashing Pressure values exceed the...

Страница 8: ...nd Non Display Temporary Mode will be set After 10 seconds display will go o To disable Non Display Temporary Mode press key for more than 4 seconds will be displayed and Non Display Temporary Mode wi...

Страница 9: ...ng part R2 type 9 Outline Dimensions Unit mm 31 4 COPAL ELECTRONICS 73 2 kPa R1 4 Fe Ni COPAL ELECTRONICS 31 4 kPa 79 2 G3 8 SUS316L 16 10 5 37 Five core shielded cable L 2000 100 Depth5 16 32 Five co...

Страница 10: ...f gauge sides Description Appllcable model Panel holder cover panel holder PG 30 35 PG 35H Holder cover set Main body Panel holder Panel holder cover 24 7 5 7 4 5 40 42 6 COPAL ELECTRONICS kPa 10 Brac...

Отзывы: