INSTALLATION AND MAINTENANCE - LSPX-FLSPX ZONE 21 - Ex tb – LSES-FLSES ZONE 22 - Ex tc
9.6 - Connecting the power supply
cables to the terminal block
The cables must be fitted with connectors suitable for the cable
cross-section and the terminal diameter.
They must be crimped in accordance with the connector
supplier’s instructions.
They must be connected with connector resting on connector
(see diagrams below):
Tightening torque (N.m) on the terminal block nuts.
Terminal
M4
M5
M6
M8
M10
M12
M16
Steel
2
3.2
5
10
20
35
65
Brass
1
2
3
6
12
20
50
The fasteners used for connecting cables must be of the same
nature as the terminals or insulator rods: do not fit steel
fastenings on brass terminals, for example.
WHEN closing the box, ensure that the seal is correctly
positioned.
As a general rule, check that no nut, washer or other
foreign body has fallen into or come into contact
with the winding.