Electric Power Generation
19
Installation and maintenance
D510 C
Digital voltage regulator
4243 en -
3.3.3.2 - Regulation mode
After entering the «Alternator Configuration» part settings, fill in the «Regulation Mode» part.
4 types of regulation are offered:
- Voltage
- Power factor (PF)
- Reactive power (kVAR)
- Manual Mode
Always setting begins with voltage regulation.
Caution, regulation of the reactive power PF and the quadrature droop can only be
enabled if there is a CT on phase U and it has been selected.