Electric Power Generation
16
Installation and maintenance
D510 C
Digital voltage regulator
4243 en -
Send the configuration to the AVR:
- check that the AVR is connected correctly
(blue LED on) at the bottom left-hand side of
the screen.
- go into the «Edit» menu.
- Go to : • PC --> D510C
• D510C --> PC
- click « PC −> D510C ».
Wait for loading to complete.
3.3.3 - New configuration
There are two possible configuration levels:
standard or expert.
By default, the software is in standard mode.
The AVR is programmed step by step. Access
to the «Regulation Mode» page is only
possible if the «Alternator Configuration»
page has been filled in. The program is
transferred to the D510C via the «Edit» menu
then «PC => D510C» or by pressing F10 on
the keypad.
This software must be used in the order
indicated below:
1. Alternator configuration
2. Regulation mode:
- Voltage regulation
- Underspeed settings
- Other types of regulation (PF, reactive
power, manual) depending on the user’s
selections.
3. Faults and digital outputs
4. Monitors
3.3.3.1 - Alternator Configuration
Open «New configuration» from the menu bar, which takes you to the «Alternator Configuration»
window. The parameters for this page are set in two parts: Alternator, Options.
The wiring scheme varies according to the characteristics specified by the user.