ID300/302 Integrated Motor Drive |
Quick Start Commissioning
5.2 Quick Commissioning with Terminal Control
5.2.1 Control Connections
5.3 Commissioning by Using a Fieldbus or Modbus RTU
With a fieldbus netword or Modbus RTU, the user needs to set
Pr 06.043
to enable the use of the
control word
Pr 06.042
and the status word
Pr 10.040
.
The control word allows the user to command the drive by setting only one parameter (
Pr 06.042
, a 15-
bit parameter).
The status word allows the user to know drive status information by reading only one parameter
(
Pr 10.040
, which is a 15-bit parameter).
For more details, refer to http://www.leroy-somer.com/documentation_pdf/5512_en.pdf
5.4 Basic Parameters of STANDARD Configuration
0 Menu
is used to group various commonly used parameters for a basic, easy setup of the drive.
All the parameters in
0 Menu
appear in other menus (advanced menus) which provide more precise
settings. For more details about
0 Menu
parameters or advanced menus, refer to http://www.leroy-
somer.com/documentation_pdf/5512_en.pdf . By default, only the first 10 parameters of
0 Menu
are
available. For 0 Menu parameter access, set
Pr 00.010
to Level 2. For advanced parameter access, set
Pr 00.010
to All Menus.
Note:
The drive must be disabled when setting parameters (Terminal 8 or Terminals 31 & 34 open).
Parameters which have no default value are Read-Only parameters.