background image

14

DT-501●

Mode 4 Display value calculation

External input pulse (Hz)

A

Parameter setting

P1 Number of blades per revolution

B

P2 Capacity per sensor blade

C

P3 Scaling

D

P4 Decimal point display

E

Equation

(A

 * 

B)

 * 

C

 * 

D

 16.                           

When You Select Mode 4 (Flowmeter Mode) for Measurement

Setting Method

Flowmeter mode

Flow sensor

Set each setting item for mode and parameter according to the following procedures.

(For the setting method of functions, refer to pages 16 and 17.)

● Setting example (For the flow display from the tank)

To display the flow ( ℓ /min) in DT-501 under the following conditions when 

the flowmeter for which the number of blades is unknown as in the figure on 

the left:

[Conditions]

● Number of blades : Unknown  

● Output of the flow sensor : 2.5cc/p

*p : Pulse

 

Normal display

Mode setting

Finish setting

The main display shows "0".

No.

Setting item

Setting range

Default setting value

Numerical value to be set according to the above example

Display

Description

P1 Number of blades per revolution

1 - 99

_ _ _ _01

1

1

Enter the number of blades of the flowmeter. If it is unknown, enter "1".

P2 Capacity per sensor blade (cc, ℓ , etc.)

0.0001 - 99999

_ 0001.0

1.0

2.5cc/p Enter the capacity per blade that the sensor can read.

P3 Scaling

0.00000 - 999999

00001.0

1

0.06 Refer to "About scaling" below.

P4 Decimal point display

0.00000 - 00000.0

00000.0

Displays to one 

decimal place

00000.0 Displays to one decimal place.

P5 Display cycle

 0.2/0.5/1.0/2.0/

5.0/10/15/30/60 sec.

_1.0_

1 sec.

1 sec. Measure using the default setting value as no special instruction is provided.

P6 Auto zero time

0.1 - 150 sec.

  _ _006.0

6 sec.

6 sec. Measure using the default setting value as no special instruction is provided.

P7 Input filter

10/30/100/0.02kHz

   _  10_ 

10kHz

10kHz Measure using the default setting value as no special instruction is provided.

  

  0

-

   0    1

-

  

  0.   0

Press and hold the SHIFT + MODE keys for 

5 seconds or more.

The main display shows the current set mode 

No. after blinking.

* When you are setting for the first time after the

   purchase of this unit, mode 1 (digital tachometer 

   mode) in the factory default setting is displayed.

Every time you press the      key, the dis-

play switches to the next mode No.

1 ● 2 ● 3 ● 4

99

Select "4".

-

   0   4

-

  

Note) If you change the mode settings, each parameter, function, and high and low set point 1 setting value will return to the factory default setting value.

• Set mode 4 (flowmeter mode).

● Setting method

(1) Mode

Press the SET key.

The display goes to mode 4 (flowmeter mode).

* For the description about the parameter functions, refer to page 20.

• Parameter setting items in mode 4 (flowmeter mode) and numerical values to be set according to the above example.

(2) Parameter

● About scaling (parameter 3)

Assuming the flow per second to be represented in the parameter 2 flow unit (cc in the example) is 

a

 (cc/s), parameter 

3 will be coefficient value when a multiplier is used to change the unit of 

a

 (cc/s) for display. 

(1) To display the value as in the original unit (cc/s)
     

a

 (cc/s)

  * 

1 ●

a

 (cc/s)

●                 ●

           Parameter 3

(2) To display the value in the unit (ℓ /min) as in the above setting
     

a

 (cc/s)

 * 

60 ÷ 1000 ●

( ℓ /min)   

                         ●                  

                   Parameter 3

*  

 * 

60      : Multiply it by 60 as it is the flow per minute.

     ÷1000  : Divide the value by 1000 as parameter is set in the unit of “cc”.

● Mode 4 (flowmeter mode) Display value calculation equation

s

www.calcert.com

[email protected]

1.888.610.7664

0

5

10

15

20

25

30

Содержание DT-501 FA-BCD

Страница 1: ...reading be sure to store this manual in a safe convenient place where operators can always refer to it easily Thank you for purchasing SHIMPO s Digital Tachometer DT 501X DT 501F For instructions on...

Страница 2: ...function settings p 17 19 Parameter settings p 8 15 Teaching function settings P7 1 Press the MEM key once to display the MAX value 2 Press the MEM key again to display the MIN value 3 Press the MEM...

Страница 3: ...densation Operating humidity 35 85 RH No condensation Operating atmosphere No corrosive gas Conforming standard RoHS Protection function Front panel IP66 or equivalent Rear terminal block IP20 Casing...

Страница 4: ...nt waterproofed but if water is splashed on the unit be sure to wipe it off the unit as soon as possible 1 Attach the provided waterproof gasket to the panel surface If waterproofing is not necessary...

Страница 5: ...d on the signal wire resulting in malfunctions Use shielded wire for input power connections with the shortest possible metal conduit Terminal block connection diagram PWR1 PWR2 E PU OC RE MG GND 12V...

Страница 6: ...nal connection Line driver Terminal block connection diagram Conduct the comparator function p 17 and memory function settings p 18 if necessary This unit requires no complicated calculation and imple...

Страница 7: ...speed is outside the input revolution speed range EE 2 is displayed and the teaching function cannot be used When the input frequency is outside the input frequency range EE 2 is displayed and the tea...

Страница 8: ...ted Circumference of the roller Revolution speed Normal display Mode setting Finish setting The main display shows 0 0 0 0 1 Press the SET key The display goes to mode 1 digital tachometer mode The nu...

Страница 9: ...000000 999999 0 F2 Low set point 1 value Sets the high set point 1 value 000000 999999 0 F3 High set point 2 value Sets the high set point 2 value 000000 999999 0 F4 Low set point 2 value Sets the low...

Страница 10: ...n Set each setting item for mode and parameter according to the following procedures For the setting method of functions refer to pages 16 and 17 As in the figure on the left bread passes through the...

Страница 11: ...tops in the elapsed timecounter mode the display will overflow after the specified time set with the auto zero function The overflow display does not mean there is a malfunction When the input signal...

Страница 12: ...em 0 00 00 0 00 0 00 1 100 sec 0 00 Select the 1 100 second display based on the operating time of the press machine P2 Measurement section 0 OFF 1 ON _ 1_ ON 0 Select 0 because the adjacent switch of...

Страница 13: ...e low set point 1 value Hour Minute Second display system 0 00 00 9 59 59 Second display system 0 00 Sets the low set point 1 value Second display system 0 00 999 99 F3 High set point 2 value Sets the...

Страница 14: ...ero time 0 1 150 sec _ _006 0 6 sec 6 sec Measure using the default setting value as no special instruction is provided P7 Input filter 10 30 100 0 02kHz _ 10_ 10kHz 10kHz Measure using the default se...

Страница 15: ...Parameter 2 setting Parameter 3 setting Parameter 4 setting Parameter 5 setting Parameter 6 setting Parameter 7 setting Finish setting The main display shows 0 00 Press the ENT key and start setting...

Страница 16: ...ost For the settings of the high set point 1 and 2 values as well as the low set point 1 and 2 values refer to Comparator Function on page 17 To the function settings The main display shows 0 0 0 1 F...

Страница 17: ...t Conditions under the low set point 1 and 2 value judgment Judgment conditions Set the high set point 1 low set point 1 high set point 2 and low set point 2 values using the function items F01 to F04...

Страница 18: ...y MAX MIN MAX MIN Normal measurement display Normal measurement display Normal measurement display Maximum value display Press the MEM key once during the normal measurement to display the maximum val...

Страница 19: ...E 3 E E 4 BTM MAX MINTEA PEAK BTM Normal display LED display test Key test Version display Mode display Test mode Press and hold the SHIFT MODE keys for 5 seconds or more Press the key to change the m...

Страница 20: ...er sensor blade cc etc Enter the capacity per blade that the sensor can read 0 0001 99999 1 0 P3 Scaling Unit coefficient value 0 00000 999999 1 P4 Decimal point display Designates the decimal point p...

Страница 21: ...99 0 F6 Judgment output timer at startup 2 Sets the time when the comparator judgment is output at startup 0 99 sec 0 sec F7 Minimum revolution speed Sets the revolution speed to be displayed as zero...

Страница 22: ...verage function is not set F8 setting value 0 When the auto zero function is activated the display becomes 0 in mode 2 and mode 3 Displays the measurement value per display cycle averaged by the frequ...

Страница 23: ...ect one out of these output options 11 12 13 14 15 16 17 18 19 20 Code Pin number Code C 4 20mA 1 19 C 4 20mA 2 20 NC 3 21 NC NC 4 22 NC NC 5 23 NC NC 6 24 NC NC 7 25 NC NC 8 26 NC V10 0 10V 9 27 V10...

Страница 24: ...log signal output offset Set the output offset value as the percentage of the output range for each analog signal __ 100 0 __100 0 0 4 20 mA 0 10 V 1 5 V 0 1 V Output range 16mA Output range 10V Outpu...

Страница 25: ...r PCS E36LMD Accessory side Plug PCS E36FS Cover PCS E36LA Both manufactured by HONDA TSUSHIN KOGYO CO LTD Positive logic negative logic available for BCD and decimal point output opted at Function 10...

Страница 26: ...output logic Set as 0 for negative logic set as 1 for positive logic decimal point output _ 0_ Negative logic _ 1_ Positive logic Negative logic F10 sets positive negative logic for BCD output Decima...

Страница 27: ...c open collector output Model CPT Output contact 1C Rated load Resistance load 250VAC 5A 100K operations 30VDC 5A 100K operations Induction load cos 0 4 250VAC 2 5A 100K operations 30VDC 2 5A 100K ope...

Страница 28: ...501XA BCD DT 501XD BCD BCD BCD output Differential input DT 501FA FVT FVT Voltage output DT 501FA FVT BCD BCD BCD output DT 501FA TRT TRT Transistor output DT 501FA TRT FVC FVC Voltage output DT 501FA...

Отзывы: