![Nidec D3-0023-B Скачать руководство пользователя страница 77](http://html1.mh-extra.com/html/nidec/d3-0023-b/d3-0023-b_user-manual_1687787077.webp)
Digistart D3: User Guide
77
Issue: G
8H – Analog Output B
Description:
Selects which information will be reported via the analog output. See Pr 8D
Analog Output A
for
details.
Options:
Current (% FLC) (default) Current as a percentage of motor full load current.
Motor Temp (%)
Motor temperature as a percentage of the motor's thermal capacity.
Motor kW (%)
Measured motor kilowatts, as a percentage of maximum kW.
Motor kVA (%)
Measured motor kilovolt amperes, as a percentage of maximum kVA.
Motor pf
Motor power factor, measured by the soft starter.
NOTE
Output B is only available if the input/output expansion card has been installed.
8I – Analog B Scale
Range:
0-20 mA
4-20 mA (default)
Description:
Selects the range of the analog output.
8J – Analog B Maximum
Range:
0% - 600%
Default:
100%
Description:
Calibrates the upper limit of the analog output to match the signal measured on an external current
measuring device.
8K – Analog B Minimum
Range:
0% - 600%
Default:
0%
Description:
Calibrates the lower limit of the analog output to match the signal measured on an external current
measuring device.
8.8.10 Group 9 - Display
9A - Languages
Options:
English
Deutsch
Français
Español
Italiano
Chinese
Description:
Selects which language the keypad will use to display messages and feedback.