Digistart D3: User Guide
59
Issue: G
Crusher Jaw
Motor Full Load Current
Start Mode
Start Ramp Time
Current Limit
Excess Start Time
Locked Rotor Time
1A
2A
2D
2B
5A
1C
Model dependent
Constant Current
10 seconds
450%
40 seconds
30 seconds
8.6 Standard menu
The standard menu provides access to commonly used parameters. For parameter details, see
Parameter
Descriptions
on page 65.
Parameter Group
Parameters
Default Value
1 - Primary Motor Settings M
1A
Motor Full Load Current
Model dependent
2 - Start/Stop Modes-1
M
2A
Start Mode
Constant Current
2B
Current Limit
350%
2C
Initial Current
350%
2D
Start Ramp Time
00:10 (minutes:seconds)
2H
Stop Mode
Coast To Stop
2I
Stop Time
00:03 (minutes:seconds)
2O
Auto-Start Type
Off
2P
Auto-Start Time
00:01 (hours:minutes)
2Q
Auto-Stop Type
Off
2R
Auto-Stop Time
00:01 (hours:minutes)
3 - Digital Inputs
M
3A
Input A Function
Starter Disable
3B
Input A Name
Starter Disable
3C
Input A Trip
Always Active
3D
Input A Initial Delay
00:00 (minutes:seconds)
3E
Input A Trip Delay
00:00 (minutes:seconds)
3F
Input B Function
Input Trip (N/O)
3G
Input B Name
Input Trip
3H
Input B Trip
Always Active
3I
Input B Initial Delay
00:00 (minutes:seconds)
3J
Input B Trip Delay
00:00 (minutes:seconds)
4 - Digital Outputs
M
4A
Relay A Action
Main Contactor
4B
Relay A On Delay
00:00 (minutes:seconds)
4C
Relay A Off Delay
00:00 (minutes:seconds)
4D
Relay B Action
Run
4E
Relay B On Delay
00:00 (minutes:seconds)
4F
Relay B Off Delay
00:00 (minutes:seconds)
4G
Relay C Action
Trip
4H
Relay C On Delay
00:00 (minutes:seconds)
4I
Relay C Off Delay
00:00 (minutes:seconds)
5 - Protection Settings
M
5A
Excess Start Time
00:20 (minutes:seconds)
5D
Phase Sequence
Any Sequence
5E
Underpower
20%
5F
Overpower
400%