GB
15
This section will help fitters to solve some of the most common
problems that may arise during installation.
No LED is on:
• Check whether the control unit is powered (check mains voltage
is present at terminals 1-2 and a voltage of approx. 24Vac at
terminals 5-6).
• Check the 2 mains fuses have not blown; if none of the Led’s is
on a serious fault has probably occurred and the control unit
should therefore be replaced.
The OK LED flashes regularly but the INPUT Led’s do not
reflect the state of the respective inputs
• Carefully check the connections on input terminals 7-13.
The manoeuvre does not start
• Check that the Led’s of the “Stop” (FCA + FCC), “Photo” and
“Photo2”, if installed, safety device are on and that the relative
command Led that is activated (“Step-By-Step”, “Open” or
“Close”) remains on for the whole duration of the command.
The gate changes direction during a manoeuvre
An inversion is caused by:
• The photocells triggering (“Photo2” during the opening
manoeuvre, or “Photo” during the closing manoeuvre); in this
case, check the connections of the photocells and check the
input Led’s.
11) What to do if .…
Mains power input
: 230 Vac 50/60 Hz
Versions /V1
: 120 Vac 50/60 Hz
Max. current for 24V services
: 200mA
Flashing lamp output
: For flashing lamps at mains voltage, maximum power 40 W
Gate open indicator output “SCA”
: For indicator lamps at 24 Vac, maximum power 2 W
Operating temperature
: -20 ÷ 70 °C
Working Time on ROBO/THOR
: Adjustable from 2.5 to >60 s, or from <50 a to >120 s with TLM
Working Time on OTTO
: Adjustable from 2.5 to >20 s, or from <20 to >40 s with TLM
Pause Time
: Adjustable from 5 to > 160 s.
On the PIU card
Partial opening time ROBO/THOR
: Adjustable from 1 to > 30 s.
Partial opening time OTTO
: Adjustable from 1 to > 14 s.
Courtesy light time
: Adjustable from 1 to > 180 s.
12) Technical specifications