6

2.

W

IRING

R

EQUIREMENTS

Single phase 240v 10A earth leakage protected power supply to where operator is mounted. If

nuisance tripping of the RCD occurs, this is due to the fact that VSD drive units inherently allow

minimal earth leakage current to flow originating from its internal power filtering which can

sometimes be enough to trip a standard RCD device.

We recommend that a selective type RCD is used, such as the Clipsal S type selective RCD.

Alternatively, the internal filtering in the VSD can be disabled. Refer to the DELTA manual for details.

Extra Low Voltage cables from operator for access control. (Shielded cable if over 8m runs).

3.

I

NSTALLATION DETAILS

After reading the previous sections in this manual, and having checked for suitable installation, proceed as follows:

Electrical Cabling

A suitably rated Isolator and 240vac power supply should be available near to where the gate operator is to be

mounted. The following diagrams will provide measurements for the positioning of conduits and the appropriate

position for mounting the operator whether a GDS 450,500,630 LI or P type.

When bringing power and control cables into the control enclosure inside the operator, please leave

enough slack in the cables, in this way, the enclosure can still be lifted up in order to see and work on

the controls easier.  To lift up control enclosure, undo wing nut on right hand side, once lifted up, re-

tighten the nut to keep enclosure in upwards position, once finished, undo wing nut, drop enclosure

back down, then re tighten wing nut.

Mechanical Installation

Ensure gate rolls easily and has been installed in a manner where there is no excessive friction or binding

occurring.

A concrete base approximately 600mm long x 300 wide x 300mm deep should be laid where the gate operator is

to be located.

IMPORTANT

ensure there are gate stops firmly installed in the fully open and closed positions.  These stops need

to be engineered and installed such that they will be strong enough to stop the gate should the limits fail at any

time

Remove the gate operator cover and position mounting plate and operator in approximate mounting location.

Use the rack to locate the operator the correct distance away from the gate rail (finer adjustment can be made

after).

Dynabolt or chemical anchor the bottom mounting plate to the concrete mounting pad using 12 x 100mm fixings.

Unscrew anticlockwise the manual disconnect knurled knob so the drive gear free wheels.

Fix the rack to the gate rail ensuring there is approximately 1mm - 2mm gap between the meshing of the teeth of

the rack and the drive gear (no more).  Move the gate by hand from one end to the other while checking that the

rack is meshing correctly with the drive gear on the operator.  Check also that the rack is centred around the

middle of the teeth on the drive cog – tighten the mounting plate nuts.

Electrical Connections

Connect an earth leakage protected 10A 240v supply to Din Rail terminals labelled A & N, Connect earth to the

earth Din Rail terminal.

Conduits for power & control need to preferably come up through the base plate 'knockout'.

Содержание GDS 450LI

Страница 1: ...nd Maintenance Manual Sliding Gate Operators Inbuilt Models GDS 450LI 630LI Range Made in Australia from Australian quality imported components DELTA VSD 10 Bennet Ave Melrose Park SA 5039 8374 3466 J...

Страница 2: ...is fixed move the gate and sight the rack moving over the pinion wheel check that most of the pinion wheel meshes with the rack Make sure rack runs freely over the pinion wheel any tights spots should...

Страница 3: ...if not reverse two of the motor wires at the inverter terminals Inverter settings can be adjusted via the keypad i e Opening speed closing speed and ramp times Automation settings operating modes are...

Страница 4: ...llation 6 10 Electrical Cabling Mechanical Installation Electrical Connections Plan view layout conduit positions CB6 Control Board layout CB 6 Control inputs mode settings 4 Delta Variable Speed Driv...

Страница 5: ...necessary signs to indicate any danger areas and automatic operation of the gate or door The operators are not designed to be used in any hazardous areas or areas subject to flooding etc All electric...

Страница 6: ...position once finished undo wing nut drop enclosure back down then re tighten wing nut Mechanical Installation Ensure gate rolls easily and has been installed in a manner where there is no excessive...

Страница 7: ...7 PLAN VIEW LAYOUT CONDUIT POSITION...

Страница 8: ...ceiver 7 Motor 2 Limit Switch Inputs 8 Terminals for Isolated 24vAC Supply 21 Firmware Version Label for Limit Switch and Control Inputs 22 Light Control Relay Interface Connector 9 Pedestrian Access...

Страница 9: ...exceed 30V A C D C 5Amps If an electromagnetic lock is used change one wire on the control board lock output to the normally closed output Use the light relay module if fitted to switch the applied v...

Страница 10: ...a pre set pedestrian access time of 5 seconds which is intended to open the motor connected to M1 output only part way If these default times do not suit your needs simply use the procedure below to a...

Страница 11: ...close command input linked to MI3 for speed setting Terminal MI3 Closing Speed Multi Step speed command input Terminal DCM command output terminal used for common PARAMETER NUMBER PARAMETER DESCRIPTIO...

Страница 12: ...se led should start to flash if they are the wrong way around turn power off to the operator wait until the inverter powers down then swap over any 2 of the motor phase wire at the inverter Turn power...

Страница 13: ...Gate Drive Systems Australia Gate Drive Systems Australia DELTA VDF EL ATA CB 6 DELTA VDF EL DELTA VDF EL ATA CB 6...

Страница 14: ...pened by hand To re engage the clutch move the gate by hand Into approx The half way position and turn the Knurled knob clockwise until it is very tight If when turning the knurled knob clockwise and...

Страница 15: ...l not run inadvertently Gate rolls freely when in manual Gate wheels and guide rollers in good condition Gate stops are installed and in good condition not loose Gate rack is tight correct clearances...

Страница 16: ...ty is negated and will not apply in the following circumstances i If no proof of date of purchase can be produced ii If the product has been used in a manner beyond its design parameters iii If the pr...

Отзывы: