8
NIBE
TM
AP-BW30
We reserve the right to make technical changes
83053706dUK – Translation of the operating manual
Installation
Observe the following when performing all work:
NOTE.
Always comply with the applicable local accident
prevention regulations, statutory regulations,
ordinances, guidelines and directives.
WARNING!
The heat pump or heat pump system
may only be installed and assembled by
qualified personnel!
NOTE.
Observe the sound levels of the respective
model.
Overview “Technical data / scope of delivery”,
“Sound” section.
INSTALLATION AREA
ATTENTION
Install the heat pump only indoors.
The installation room must be frost-free and
dry.
WARNING!
Please note and follow the respective
relevant local standards, directives and
regulations applicable, especially the
minimum volume necessary depending
on the refrigerant capacity of the relevant
heat pump system (EN 378-1).
Refrigerant
Limit
R 134a
0.25 kg/m³
R 404A
0.48 kg/m³
R 407C
0.31 kg/m³
R 410A
0.44 kg/m³
Overview “Technical data / scope of delivery”,
“General unit data” section.
Minimum volume =
Refrigerant capacity [kg]
Limit [kg/m³]
NOTE.
If several heat pumps of the same type
are installed, only one heat pump must be
considered.
If several heat pumps of different types are
installed, the heat pump with the largest
refrigerant capacity must be considered.
TRANSPORT TO INSTALLATION LOCATION
Before transporting the heat pump to the final
installation location the packaging and wooden
frame can be dismantled.
To do this, remove the facing panels on the long
sides, undo the wooden boards and remove the
two machine screws (M8) in each of the sides.
You can now lift the unit with the help of a pallet
truck or fork lift truck and transport it to its final
installation location.
NOTE.
The unit has ground clearance for easy access
from all sides
NOTE.
The baseplate is 76 cm wide, so that the heat
pump can be transported through a standard
door opening.