Chapter 4
Connecting the Signals
©
National Instruments Corporation
4-45
The following recommendations apply for all signal connections to the
device:
•
Separate NI 6052E signal lines from high-current or high-voltage
lines. These lines can induce currents in or voltages on the NI 6052E
signal lines if they run in parallel paths at a close distance.
To reduce the magnetic coupling between lines, separate them by a
reasonable distance if they run in parallel or run the lines at right angles
to each other.
•
Do
not
run signal lines through conduits that also contain power lines.
•
Protect signal lines from magnetic fields caused by electric motors,
welding equipment, breakers, or transformers by running them
through special metal conduits.
Refer to the NI Developer Zone tutorial,
Field Wiring and Noise
Consideration for Analog Signals
, available at