PSH150
user manual rev4
Page 14/15
Wall / Panel mounting
It is possible install directly on panel or wall using the appropriate fixing points according the above image.
Recommended connecting cable
Recommended Tightening torque
Input / output connections
0.5-0.6Nm
4.42-5.30 lbf in
Auxiliary connections
Insertion force per pole
Max 3N or 0.674 lbf
Withdrawal force per pole
Min 1.5N or 0.337 lbf
Input / output connections
Solid: 2.5mm² / 12AWG
Stranded:1.5mm² / 12AWG
L: 6.0-7.5mm / 0.24-0.30in
Auxiliary connections
Solid: 0.5mm² / 20AWG
Stranded: 0.5mm² / 20AWG
L: 7.0-8.0mm / 0.27-0.315in
Input connection
AC Line
DC Line
Input protection
Fuses MCB 6A C curve
For USA and Canada, use the fuse type closest to the European equivalent type.
Surge protection:
it is strongly recommended to provide external surge arresters (SPD) according to local regulations.
Environment
Operating temperature
Derating
-
40°C…70°C
5…95% r.H. non condensing
Overtemperature protection
See
Figure 3
and
Figure 4