6.10
MS-2101
Chapter 6
Setpoint Values
MESSAGE NO:
S3-09
APPLIES TO:
Interface Module
DEFAULT VALUE: advanced userVALUE RANGE: advanced user, normal user
DISPLAY MODE: All
RESTRICTIONS: None
This function determines what messages are displayed. If set to
advanced user
,
all messages are displayed. If set to
normal user
, only the basic messages are
displayed. Each message listed in this chapter shows the Display Mode required
to see the message.
Advanced
indicates that you must set the display mode to
advanced user
to view the message.
MESSAGE NO:
S3-10
APPLIES TO:
Interface Module
DEFAULT VALUE: System status VALUE RANGE: See values below
DISPLAY MODE: Advanced
RESTRICTIONS: Heater Temp messages are
not displayed if Heater
setpoint is
off
.
This function specifies the information that will be displayed when no key has
been pressed for the Display Timeout interval as described below.
VALUE
INFORMATION DISPLAYED
System status
Alarm status
Heater status
Heater on or off
Heater temp
Control temperature
MESSAGE NO:
S3-11
APPLIES TO:
Interface Module
DEFAULT VALUE: 60 s
VALUE RANGE: 5 to 600 s, off
DISPLAY MODE: Advanced
RESTRICTIONS: None
This function sets the length of time, from the last key press, to automatically
return to the Default Display information. To disable this function, set the value to
off
.
MESSAGE NO:
S3-12
APPLIES TO:
Interface Module
DEFAULT VALUE: 3 s
VALUE RANGE: 1 to 10 s
DISPLAY MODE: Advanced
RESTRICTIONS: None
This function sets the length of time between the display of successive messages.
Select a value that is comfortable for the viewing speed of the operator.
MESSAGE NO:
S3-13
APPLIES TO:
Control Module
DEFAULT VALUE: 1
VALUE RANGE: 1-250
DISPLAY MODE: Advanced
RESTRICTIONS: None
This function changes the Module Number of the Control Module. If a controller
is to communicate along with other modules to a central computer or display,
each module must have a unique address to ensure only one module attempts to
communicate with the remote display at any time. The address for communication
is the module number.
DEFAULT DISPLAY:
System Status
"
DISPLAY TIMEOUT:
60 seconds
"
SCAN TIME:
2 seconds
"
SET MODULE
NUMBER: 1
"
DISPLAY MODE:
advanced user
"
Содержание MASTERTRACE MS-2101
Страница 1: ...MASTERTRACE MS 2101 OPERATOR S MANUAL HEAT TRACING CONTROL ...
Страница 11: ...1 8 MS 2101 Chapter 1 Product Overview Figure 1 8 Hardware Block Diagram ...
Страница 13: ...2 2 MS 2101 Chapter 2 Installation Figure 2 2 Power Board Layout Figure 2 1 Main Board Layout ...
Страница 23: ...4 2 MS 2101 Chapter 4 Front Panel Operation Figure 4 2 Contrast Control Figure 4 1 Display Front View ...