6.11
MS-2101
Chapter 6
Setpoint Values
MESSAGE NO:
S3-14
APPLIES TO:
Control Module
DEFAULT VALUE: no
VALUE RANGE: yes, no
DISPLAY MODE: Advanced
RESTRICTIONS: None
This function resets all values of the Control Module to the default values. Select
yes
to proceed. Select
yes
again to confirm.
This message confirms that the Control Module was reset.
MESSAGE NO:
S3-15
APPLIES TO:
Interface Module
DEFAULT VALUE: 1200
VALUE RANGE: 600,1200,2400,4800,9600
DISPLAY MODE: Advanced
RESTRICTIONS: None
This function sets the communication baud rate for the RS-485 serial port. All
controllers connected to the same data highway must operate at the same baud
rate.
MESSAGE NO:
S4-01
APPLIES TO:
Interface Module
DEFAULT VALUE: N/A
VALUE RANGE: N/A
DISPLAY MODE: Advanced
RESTRICTIONS: None
This message displays the name of the sub-menu when entered.
MESSAGE NO:
S4-02
APPLIES TO:
Selected Control Module
DEFAULT VALUE: disabled
VALUE RANGE: 1 to 24 hrs, disabled,
on continuously
DISPLAY MODE: Advanced
RESTRICTIONS: None
This function manually controls of the alarm output for maintenance purposes. For
normal operation, set to
disable
. If you select a period of time, the alarm output is
forced into alarm state for the selected interval. If you select
on continuously
, the
alarm output is forced into alarm state until you select
disabled
. Alarm state is
determined by ALARM CONFIG function settting.
MESSAGE NO:
S4-03
APPLIES TO:
Selected Heater
DEFAULT VALUE: disabled
VALUE RANGE: 1 to 24 hrs, disabled,
on continuously
DISPLAY MODE: Advanced
RESTRICTIONS: None
This function manually overrides heater control for maintenance purposes. For
normal operation, set to
disable
. If you select a period of time, the heater is forced
on
for the selected interval. If you select
on continuously
, the heater is forced on
until you select
disabled
.
Setpoint Tests
BAUD RATE:
1200
"
SETPOINTS
TEST
ALARM TEST:
disabled
"
HEATER TEST:
disabled
"
MODULE
RESET
yes [STORE]
ARE YOU SURE?
no
"
RESET CONTROL
MODULE? no
"
yes [STORE]
Содержание MASTERTRACE MS-2101
Страница 1: ...MASTERTRACE MS 2101 OPERATOR S MANUAL HEAT TRACING CONTROL ...
Страница 11: ...1 8 MS 2101 Chapter 1 Product Overview Figure 1 8 Hardware Block Diagram ...
Страница 13: ...2 2 MS 2101 Chapter 2 Installation Figure 2 2 Power Board Layout Figure 2 1 Main Board Layout ...
Страница 23: ...4 2 MS 2101 Chapter 4 Front Panel Operation Figure 4 2 Contrast Control Figure 4 1 Display Front View ...