6.9
MS-2101
Chapter 6
Setpoint Values
MESSAGE NO:
S3-05
APPLIES TO:
Interface Module
DEFAULT VALUE: MECH:NC
VALUE RANGE: MECH:NO SS:N/A
SS:N/A
MECH:NO SS:N/A
MECH:NC SS:N/A
MECH:NC SS:N/A
DISPLAY MODE:
Advanced
RESTRICTIONS: None
This function configures the alarm contacts for normally open (NO) or normally
closed (NC). MECH refers to the mechanical alarm contact on terminals 20 and 21
of the Control Module. SS refers to the solid-state alarm contact that is not
available on board. In
NO
mode, the contact closes during alarm condition. In
NC
mode, the contact opens during alarm condition.
MESSAGE NO:
S3-06
APPLIES TO:
Interface Module
DEFAULT VALUE: no
VALUE RANGE: low temp, high temp
low current, high current
gf alarm, RTDA failure
RTDB failure, switch fail
low voltage, high voltage
continuity
yes, no for each alarm
DISPLAY MODE: Advanced
RESTRICTIONS: None
This function configures each alarm as latching or non-latching. Pressing
[STORE] toggles the cursor between alarm selection and yes or no selection.
Alarms selected as
yes
will be latched. Latching alarms will remain on the display
eventhough the alarm condition no longer exist. To clear the alarm, you must press
[STATUS] to display the alarm and press [RESET]. When the actual and alarm
setpoint values are displayed, the actual value is the pre-alarm actual value.
Tracecheck, ground fault trip and test alarms are latched only and not user
definable.
MESSAGE NO:
S3-07
APPLIES TO:
Interface Module
DEFAULT VALUE: alarm:off
VALUE RANGE: alarm:off, alarm:on
flash/on, flash/off
DISPLAY MODE: Advanced
RESTRICTIONS: None
This function determines the response of the alarm light output to an alarm. The
alarm light output is design to drive a 5Vdc LED. If the value is set to
alarm off
,
the alarm light is
on
in a no alarm condition and turns
off
when alarms are
present. The
alarm off
setting works best with a green LED for fail-safe mode
where loss of power or a burnt out LED generates an alarm condition. Value
alarm on
, turns the alarm light
off
in a no alarm condition and turns
on
when
alarms are present. Value
alarm flash/on
flashes the alarm light when alarms are
present and turns
on
the alarm light when there are no alarms. Value
alarm flash/
off
flashes the alarm light when alarms are present and turns
off
the alarm light
when there are no alarms.
MESSAGE NO:
S3-08
APPLIES TO:
Interface Module
DEFAULT VALUE: Celsius
VALUE RANGE: Celsius, Fahrenheit
DISPLAY MODE: Advanced
RESTRICTIONS: Heater Setpoint must not be
off
.
This function sets the units of measure for temperature. All temperatures are
displayed in the selected units of either degrees Celsius (°C) or degrees Fahrenheit
(°F).
ALARM CONTACTS:
MECH:NO
"
SS:N/A
"
ALARM LIGHT MODE:
alarm: off
"
TEMPERATURE UNITS:
Celcius
"
ALARM LATCHING:
low temp
"
yes
"
Содержание MASTERTRACE MS-2101
Страница 1: ...MASTERTRACE MS 2101 OPERATOR S MANUAL HEAT TRACING CONTROL ...
Страница 11: ...1 8 MS 2101 Chapter 1 Product Overview Figure 1 8 Hardware Block Diagram ...
Страница 13: ...2 2 MS 2101 Chapter 2 Installation Figure 2 2 Power Board Layout Figure 2 1 Main Board Layout ...
Страница 23: ...4 2 MS 2101 Chapter 4 Front Panel Operation Figure 4 2 Contrast Control Figure 4 1 Display Front View ...