7.0 Troubleshooting

• Meter Display Errors: In the event the LCD display gets out of sync with the micro-controller and displays incorrect 

information, a simple fix is to power cycle the LCD. To power cycle the meter without disconnecting the load: first ensure 

the rectifiers are on, slide the breaker to OFF position then slide the meter power to ‘Battery’ then back to ‘Rectifier’. This will 

briefly disconnect power to the meter and allow a safe power cycling and clear the display error. Turn on battery breaker.
• LVD Stability Issues After Settings Change: If the LVD contactor cycles frequently after making changes to the LVD 

default settings, the ULM-100 can be restored to factory settings to aid in troubleshooting (see 5.26 and the menu diagram 

for details). 

8.0 Specifications

Electrical 

Nominal System Voltage: 

12, 24 or 48 VDC

Voltage Range:

 8 to 65 vdc

Grounding:

 Positive or Negative (polarity insensitive)

Maximum Continuous Current:

 100 Amps DC

Battery Breaker:

 100 Amps with handle guard

Low Voltage Battery Disconnect:

 100 Amp, solid state (FET)

Factory Default:

LVD Set Points

12 Volt

24 Volt

48 Volt

Disconnect

10.4V

21.0V

42.0V

Connect

12.0V

24.5

49.0V

Factory Default LVD Pre-Disconnect Alarm Threshold (Adjustable):

System Voltage

12V

24V

48V

LVD Pre- Disconnect

11.2V

22.8V

45.5V

6

Figure 6: ULM-100 and Power Module

Mechanical

Chassis:

 Aluminum with vinyl lamination, black powder   

              coat front panel

Terminals:

 Plated copper. Landings for up to three 

                   rectifier inputs, with separate battery & load      

                   terminals

Rack Size:

 19”, 1U

Cooling:

 Convection

Dimensions:

 1.75” H x 19” W  x 11” D 

Weight:

 6.25 Lbs.

Environmental

Operating Temperature range:

 0 to +60°C

* Fuse Hot near 

battery on long 

cable runs

Содержание ULM-100

Страница 1: ...3 Backlighting Adjustment 4 4 0 Wiring 2 5 24 Temperature Monitoring 4 4 1 Rectifier Input 2 5 25 Meter Power Source Selector 4 4 2 Battery Input 2 5 26 Restore to Factory Settings 5 4 3 Load Output 2...

Страница 2: ...Head bolt for rectifier battery input load connection 10 split lock washer one per 1 4 20 Hex Head bolt above 1 Installation Operation Manual 3 0 Mounting 3 1 Rack Ears One pair of rack ears for 19 ra...

Страница 3: ...a the Molex six conductor alarm wire pigtail included with the ULM 100 See section 5 12 5 13 for information on setting Pre disconnect and LVD activation thresholds 5 0 Operation Adjustments Figure 3...

Страница 4: ...el at which the battery will be re connected after a dis connect event when AC power is restored Pre LVD Alarm Level at which the pre LVD alarm contact triggers as an early warning for a low battery d...

Страница 5: ...6 0 Connecting Rectifier Types The ULM 100 will accept any filtered rectifier input s providing total rectifier amperage does not exceed 100 Amps See Figure 5 and 6 for wiring examples of Newmar Unity...

Страница 6: ...o factory settings to aid in troubleshooting see 5 26 and the menu diagram for details 8 0 Specifications Electrical Nominal System Voltage 12 24 or 48 VDC Voltage Range 8 to 65 vdc Grounding Positive...

Страница 7: ...P O Box 1306 Newport Beach California 92663 Phone 714 751 0488 Fax 714 957 1621 E Mail techservice newmarpower com www newmartelecom com 7 9 0 Outline Mounting Dimensions...

Отзывы: