5.11

 Manual/Auto selector switch: The LVD selector switch sets the way the LVD circuit functions.

• Manual connect - Battery always online

• Automatic - LVD function enabled (factory default)

• Manual disconnect - Battery always offline

5.12

 LVD Adjustment: The ULM-100 offers easy adjustment of both dis-connect and re-connect  LVD settings without the 

need for an external, adjustable power supply. These thresholds can be selected from the SETTINGS page using the menu 

knob, the default factory setting for the particular item is also displayed. A press on the menu knob will save the settings 

and is retained even after powering down the unit. LVD threshold adjustment can be made while the system is operating.

5.13

 LVD Alarms: Pre-disconnect & disconnect - Two external alarms can be triggered by the ULM-100: the Pre-disconnect 

(‘PRELVD’) and the LVD dis-connect (‘LVDDISCON’). The LVD Pre-disconnect alarm is a warning to an impending battery 

disconnect. It is triggered by an adjustable voltage thresholds set above the LVD dis-connect  threshold and below the 

re-connect threshold. The LVD dis-connect alarm is automatically set using the LVD dis-connect threshold (see 5.12). Both 

alarms will trigger the LED Alarm light. 

5.14 Voltage Level Mapping - 12 VDC example shown

12.5v NORMAL VOLTAGE

12.3v LVD RE-CONNECT 

(ADJUSTABLE)

11.6v PRE-LVD ALARM 

(ADJUSTABLE)

11.0v LVD DIS-CONNECT 

(ADJUSTABLE)

Normal Voltage - 

Typical system voltage with rectifiers supplying load(s), batteries not deeply discharged.

LVD Re-Connect - 

Level at which the battery will be re-connected after a dis-connect event when AC power is restored.

Pre-LVD Alarm - 

Level at which the pre-LVD alarm contact triggers as an early warning for a low battery disconnect. (See 

Specification Section 8.0 for factory default.)

LVD Dis-Connect - 

Minimum allowable battery voltage level has been reached and will disconnect battery to prevent 

damage. Will also trigger LVD alarm. (See Specification Section 8.0 for factory default.)

5.2

 

Meter

Figure 4: LCD Home Screen

5.21

 The home screen shows DC voltage, DC current and Ambient temperature in degrees Celsius. The  display always 

returns to the home screen after 30 seconds of inactivity. A push of the menu button will display the alarm screen and 

rotating the knob will send it to adjacent display pages.

5.22

 Plant Current Monitoring: The total current being produced by the rectifier(s) connected is displayed on the main 

screen. This includes current drawn by the load and battery charging current.

5.23

 Back Lighting: The ULM-100 allows the user to adjust LCD backlight level to match environment lighting or suit user 

preferences. Changes can be made in the settings menu and is adjustable from 20% to 100% levels.

5.24

 Temperature Monitoring: Ambient temperature is displayed on the home screen in Celsius and on the temperature 

screen in both Fahrenheit and Celsius. The sensor is located on the front panel next to the alarm LED.

5.25

 Meter Power Source Selector: The LCD meter can be powered from the rectifier side or the battery side by using the 

selector switch. Powering the meter from the rectifier side(default) causes the ULM-100 to completely shutdown during a 

Low battery voltage disconnect thus reducing battery drain. Powering from the battery side will allow the LCD meter to 

continue operating even with a an LVD disconnect event.

4

Содержание ULM-100

Страница 1: ...3 Backlighting Adjustment 4 4 0 Wiring 2 5 24 Temperature Monitoring 4 4 1 Rectifier Input 2 5 25 Meter Power Source Selector 4 4 2 Battery Input 2 5 26 Restore to Factory Settings 5 4 3 Load Output 2...

Страница 2: ...Head bolt for rectifier battery input load connection 10 split lock washer one per 1 4 20 Hex Head bolt above 1 Installation Operation Manual 3 0 Mounting 3 1 Rack Ears One pair of rack ears for 19 ra...

Страница 3: ...a the Molex six conductor alarm wire pigtail included with the ULM 100 See section 5 12 5 13 for information on setting Pre disconnect and LVD activation thresholds 5 0 Operation Adjustments Figure 3...

Страница 4: ...el at which the battery will be re connected after a dis connect event when AC power is restored Pre LVD Alarm Level at which the pre LVD alarm contact triggers as an early warning for a low battery d...

Страница 5: ...6 0 Connecting Rectifier Types The ULM 100 will accept any filtered rectifier input s providing total rectifier amperage does not exceed 100 Amps See Figure 5 and 6 for wiring examples of Newmar Unity...

Страница 6: ...o factory settings to aid in troubleshooting see 5 26 and the menu diagram for details 8 0 Specifications Electrical Nominal System Voltage 12 24 or 48 VDC Voltage Range 8 to 65 vdc Grounding Positive...

Страница 7: ...P O Box 1306 Newport Beach California 92663 Phone 714 751 0488 Fax 714 957 1621 E Mail techservice newmarpower com www newmartelecom com 7 9 0 Outline Mounting Dimensions...

Отзывы: