5.26

 Restore to Factory Settings: The ULM-100 comes with default factory settings that will work for most applications. 

This feature will clear all user setting changes back to factory settings. This is particularly useful in the event the ULM-

100 contactor begins  cycling. Example: Connect and Disconnect thresholds set too close toghether. The ‘Restore Setting’ 

feature can be activated in the settings menu.

5.3

 Battery Circuit Breaker: The Hot side of the battery input goes to a front panel mounted 100 Amp circuit breaker 

labeled ‘BATTERY’. This circuit breaker incorporates auxiliary contacts which will alert the user via the LCD display (‘Battery 

offline’) and red ‘Alarm’ LED, should the breaker trip or be placed in to the OFF position inadvertently.

5.4

 Alarm LED: This red LED will illuminate when any of the following conditions occur:       

• Battery circuit breaker in OFF position

• LVD Pre-disconnect threshold crossed (see section 5.13 for more info)

• LVD activation- manually or automatically

6.0 Connecting Rectifier Types

 

The ULM-100 will accept any filtered rectifier input (s) providing total rectifier amperage does not exceed 100 Amps.  See 

Figure 5 and 6 for wiring examples of Newmar Unity Rectifier Shelf  (URS) and Power Modules (PM Series).

               

6.1

 Unity Rectifier Shelf (URS): The URS has two sets of output terminals. Both are marked ‘OUTPUT/BATTERY’. One  set uses 

a barrier style terminal block with # 6 screw terminals located near the optional UFP-5 fuse panel location and the other 

is a european style terminal block on the opposite end of URS rear panel which will accommodate up to 8 AWG wire size. 

The ULM-100 Rectifier Input can be connected to either one of these two sets of output terminals.

               

UFP-5 Note:

 If using the optional Unity UFP-5 GMT Fuse Distribution Panel, the UFP-5 Hot & RTN/GND input leads will have 

to be extended with a pair of 14 AWG wires and crimp butt connectors. Connect extended UFP-5 input wires to the ULM-

100 LOAD terminals.

Figure 5: ULM-100 and Unity Rectifier Shelf (URS) with Optional UFP-5 Wiring Diargram

 6.2

 Power Module (PM Series): One or more Newmar PM Series Power Modules can be connected to the ULM-100 Rectifier 

Input (100 Amps max. total). Use the ‘Vout’ or diode isolated terminal when connecting 2 or more PM’s in parallel. Figure 

6, ULM-100 and Power Module wiring diagram - next page.

5

Содержание ULM-100

Страница 1: ...3 Backlighting Adjustment 4 4 0 Wiring 2 5 24 Temperature Monitoring 4 4 1 Rectifier Input 2 5 25 Meter Power Source Selector 4 4 2 Battery Input 2 5 26 Restore to Factory Settings 5 4 3 Load Output 2...

Страница 2: ...Head bolt for rectifier battery input load connection 10 split lock washer one per 1 4 20 Hex Head bolt above 1 Installation Operation Manual 3 0 Mounting 3 1 Rack Ears One pair of rack ears for 19 ra...

Страница 3: ...a the Molex six conductor alarm wire pigtail included with the ULM 100 See section 5 12 5 13 for information on setting Pre disconnect and LVD activation thresholds 5 0 Operation Adjustments Figure 3...

Страница 4: ...el at which the battery will be re connected after a dis connect event when AC power is restored Pre LVD Alarm Level at which the pre LVD alarm contact triggers as an early warning for a low battery d...

Страница 5: ...6 0 Connecting Rectifier Types The ULM 100 will accept any filtered rectifier input s providing total rectifier amperage does not exceed 100 Amps See Figure 5 and 6 for wiring examples of Newmar Unity...

Страница 6: ...o factory settings to aid in troubleshooting see 5 26 and the menu diagram for details 8 0 Specifications Electrical Nominal System Voltage 12 24 or 48 VDC Voltage Range 8 to 65 vdc Grounding Positive...

Страница 7: ...P O Box 1306 Newport Beach California 92663 Phone 714 751 0488 Fax 714 957 1621 E Mail techservice newmarpower com www newmartelecom com 7 9 0 Outline Mounting Dimensions...