Table 1: Wire Size Chart
Amperage
Minimum Wire Size in AWG
1-10A
#16
11-20A
#14
21-30A
#12
31-35A
#10
36-50A
#8
51-70A
#6
71-90A
#4
91-100A
#2
4.4
Alarms: Pre-disconnect & Disconnect- Two sets of Form C alarm contacts are provided for the following: Pre-LVD
Disconnect & LVD Disconnect. Wiring is via the Molex six conductor alarm wire pigtail included with the ULM-100. See
section 5.12 & 5.13 for information on setting Pre-disconnect and LVD activation thresholds.
5.0 Operation & Adjustments
Figure 3: LCD Menu
5.1
Low Voltage Disconnect: The ULM-100 incorporates a 100 Amp solid state LVD circuit which automatically removes
the battery when battery voltage drops to a pre-set DISCONNECT threshold (or when manually activated- see section
5.11) and automatically re-connects the battery when battery voltage rises above the selected CONNECT threshold (see
Specification 8.0 for default LVD thresholds and adjustment ranges)