FIGURE 7: Circuit Breaker Installation

1)

 Shut off all power to the PFM and slide the LVBD switch on the front panel into the “MANUAL DISCONNECT” position 

before proceeding. Remove the two flat head screws on either side of the breaker retaining plate and pull firmly 

outward to remove it. 

Note: The protective circuit breaker clear plastic toggle handle cover is not shown in the above diagram

Installation is optional. If it has already been installed, it is not necessary to remove the cover in order to remove the 

retaining plate.

2)

 Remove the plastic breaker hole plugs as necessary.

3)

 

Prior to installing circuit breakers, make note of the following: 

The conductor for each breaker position runs straight through 

to the rear of the PFM so that the breaker in Position 1 (as you face the front) is on the far left, and the Position 1 output 

terminal (as you face the rear) is on the far right, and so on with each breaker/output terminal position reversed from front 

to back.

4) 

Install each circuit breaker into the PFM with “OFF” facing upward (toggle down) by lining up the push-in studs of the 

breakers with the internal mating holes inside the breaker receptacle and pushing firmly into place. The two top auxiliary 

contact terminals in the middle of the breaker should press against the mating clips. The bottom auxiliary contact is 

unused in this installation.

5)

 Ease the breaker retaining plate back into position over the breakers and onto the PFM. The holes in the retaining plate 

are beveled to help adjust the breakers into position, but it may be necessary to retract the plate and nudge breakers 

individually to achieve the necessary alignment.

6)

 Replace the retaining plate mounting screws.

7)

 Restore power to the PFM (if all other aspects of installation have been completed) and return the LVBD switch to the 

“AUTO” position.

Circuit Breaker Finger Guard Cover, Labeling

Installation of the circuit breaker toggle handle finger guard cover is optional. Use the provided 6/32-1/4" screws and 

spacer for mounting the cover onto the retaining plate. Blank labels are provided with the packaging to be placed on the 

clear Finger Guard cover over each position for identifying each circuit function.

Note: 100 and 75 amp breakers may not be 

installed side by side. There must be an open 

space or a breaker rated at 50 amps or less 

between them.

Breaker Retaining Plate

Retaining Plate Mounting Screw 

(one on each side)

Breaker Hole Plugs 

Finger Guard Cover

Breaker Push-In Studs

Plug-In Circuit Breaker

Auxiliary Contacts  

(COM and N.O. used)

Breaker Mating Holes

Aux. Contact Mating Clips

Finger Guard Mounting Screw and Spacer 

(one on each side)

Содержание PFM-500

Страница 1: ...ng E Output Wiring 5 1 Unswitched Output 2 Switched Output F Battery Wiring 6 G Status and Alarm Contact Wiring 7 H Chassis Grounding 8 I Circuit Breakers 8 1 Breaker Installation 2 Breaker Functions...

Страница 2: ...TERY POSITIVE NEGATIVE OR FLOATING GROUND STATUS CONTACTS RETURN GND INPUT 1 INPUT 2 INPUT 3 LVD SUMMARY ALARM OUTPUT INPUT 4 INPUT 5 INPUT 6 NC NO C CONTACTS SHOWN IN FAILED POSITION 1 2 3 1 2 3 1 2...

Страница 3: ...osing flush mounting C Bus Bar Mounting The PFM is shipped with a rackmount ground bus bar assembly kit BBA 800 The bus bar is typically mounted on the rear of the rack and is designed for installatio...

Страница 4: ...Hot Wire to POSITIVE OUTPUT Terminal Positive Ground Systems Connect Ground Wire to POSITIVE OUTPUT Terminal and Hot Wire to NEGATIVE OUTPUT Terminal Power Plugs shown present only if using NEWMAR QC...

Страница 5: ...for proper PFM input wire gauges 3 A return ground wire must also be run from the BBA bus bar or other grounding point to the terminal on the PFM labeled RETURN GND This is not a system ground rather...

Страница 6: ...s requires installation of a model PBA plug in breaker available from NEWMAR at that position See section II I Fig 7 for installation details and breaker functions See section VII for available ampera...

Страница 7: ...ness is designed for installations which employ NEWMAR Power Modules though it may be modified for use with other types of equipment as well provided they are equipped with Form C or Normally Open N O...

Страница 8: ...nd a summary alarm from the DST is required this may be accomplished through parallel wiring of the status wires Please contact the factory for information on how to perform this modification When wir...

Страница 9: ...reaker receptacle and pushing firmly into place The two top auxiliary contact terminals in the middle of the breaker should press against the mating clips The bottom auxiliary contact is unused in thi...

Страница 10: ...e or the battery side by using the selector switch on front panel Powering the meter from the rectifier side default causes the PFM 500 to completely shutdown during a Low Battery Voltage Disconnect t...

Страница 11: ...8 Fax 714 856 9679 E Mail techservice newmarpower com PoweringTheNetwork com C LCD Display 1 Digital Meter Programming Sequence Flow Chart Figure 8 Digital Meter Programming Sequence Flow Chart see pa...

Страница 12: ...voltage disconnect Screen press programming button to enter set mode rotate knob to change push to confirm setting See page 13 for detailed directions 4B LVD voltage connect Screen press programming...

Страница 13: ...ngs and is retained even after powering down the unit LVD threshold adjustment can be made while the system is operating 3 LVD Alarms Pre disconnect disconnect Two external alarms can be triggered by...

Страница 14: ...Section III D for LVD adjustment procedure 4 PFM load circuit breaker tripped Breaker is in mid trip position Note Breaker will not activate the ALARM L E D if manually switched into the off position...

Страница 15: ...power com Anytime We are happy to consult with you to resolve any problems or questions you may have If during consultation it appears the PFM must be returned to the factory for repair we will issue...

Страница 16: ...low TEMPERATURE RATING 0 C to 60 C CASE SIZE H x W x D 3 5 x 19 or 23 x 20 5 LVD SPECIFICATIONS Factory set actuation voltages 12 Volt 24 Volt 48 Volt Disconnect 10 4V DC 21 0V DC 42 0V DC Connect 12...

Отзывы: