D) LVD Operation and Programming

Low Voltage Disconnect: The PFM-500 incorporates a 500 amp LVD circuit which automatically removes the battery 

when battery voltage drops to a pre-set DISCONNECT threshold (or when manually activated- see section 5.11) and 

automatically re-connects the battery when battery voltage rises above the selected CONNECT threshold (see Specification 

8.0 for default LVD thresholds and adjustment ranges)

1)

 

Manual/Auto Selector Switch:

 The LVD selector switch, located on front panel, sets the way the LVD circuit functions.

• Manual connect - Battery always online

• Automatic - LVD function enabled (factory default)

• Manual disconnect - Battery always offline

2)

 

LVD Adjustment:

 The PFM-500 offers easy adjustment of both dis-connect and re-connect  LVD settings without the need 

for an external, adjustable power supply. These thresholds can be selected on the front panel meter from the SETTINGS 

page (see Flow Chart on page 10) using the menu knob, the default factory setting for the particular item is also displayed. 

A press on the menu knob will save the settings and is retained even after powering down the unit. LVD threshold 

adjustment can be made while the system is operating.

3)

 

LVD Alarms:

 Pre-disconnect & disconnect - Two external alarms can be triggered by the PFM-500: the Pre-disconnect 

(‘PRELVD’) and the LVD dis-connect (‘LVDDISCON’). The LVD Pre-disconnect alarm is a warning to an impending battery 

disconnect. It is triggered by an adjustable voltage thresholds set above the LVD dis-connect  threshold and below the 

re-connect threshold. The LVD dis-connect alarm is automatically set using the LVD dis-connect threshold (see 5.12). Both 

alarms will trigger the LED Alarm light. 

4) LVD Voltage Sequencing Example - 12 VDC shown

12.5v NORMAL SYSTEM VOLTAGE

12.3v LVD RE-CONNECT 

(ADJUSTABLE)

11.6v PRE-DISCONNECT WARNING ALARM 

(ADJUSTABLE)

11.0v LVD DIS-CONNECT 

(ADJUSTABLE)

a) Normal Voltage: 

Typical system voltage with rectifiers supplying load(s), batteries not deeply discharged.

b) LVD Re-Connect: 

Level at which the battery will be re-connected after a dis-connect event when system voltage is 

restored.

c) Pre-LVD Alarm: 

Level at which the pre-LVD alarm contact triggers as an early warning for impending low battery 

disconnect. (See Specification Section 8.0 for factory default.)

d) Battery Dis-Connect: 

Minimum allowable battery voltage level has been reached and will disconnect battery to 

prevent damage. Will also trigger LVD alarm. (See Specification Section VI: Specifications for factory default.)

Содержание PFM-500

Страница 1: ...ng E Output Wiring 5 1 Unswitched Output 2 Switched Output F Battery Wiring 6 G Status and Alarm Contact Wiring 7 H Chassis Grounding 8 I Circuit Breakers 8 1 Breaker Installation 2 Breaker Functions...

Страница 2: ...TERY POSITIVE NEGATIVE OR FLOATING GROUND STATUS CONTACTS RETURN GND INPUT 1 INPUT 2 INPUT 3 LVD SUMMARY ALARM OUTPUT INPUT 4 INPUT 5 INPUT 6 NC NO C CONTACTS SHOWN IN FAILED POSITION 1 2 3 1 2 3 1 2...

Страница 3: ...osing flush mounting C Bus Bar Mounting The PFM is shipped with a rackmount ground bus bar assembly kit BBA 800 The bus bar is typically mounted on the rear of the rack and is designed for installatio...

Страница 4: ...Hot Wire to POSITIVE OUTPUT Terminal Positive Ground Systems Connect Ground Wire to POSITIVE OUTPUT Terminal and Hot Wire to NEGATIVE OUTPUT Terminal Power Plugs shown present only if using NEWMAR QC...

Страница 5: ...for proper PFM input wire gauges 3 A return ground wire must also be run from the BBA bus bar or other grounding point to the terminal on the PFM labeled RETURN GND This is not a system ground rather...

Страница 6: ...s requires installation of a model PBA plug in breaker available from NEWMAR at that position See section II I Fig 7 for installation details and breaker functions See section VII for available ampera...

Страница 7: ...ness is designed for installations which employ NEWMAR Power Modules though it may be modified for use with other types of equipment as well provided they are equipped with Form C or Normally Open N O...

Страница 8: ...nd a summary alarm from the DST is required this may be accomplished through parallel wiring of the status wires Please contact the factory for information on how to perform this modification When wir...

Страница 9: ...reaker receptacle and pushing firmly into place The two top auxiliary contact terminals in the middle of the breaker should press against the mating clips The bottom auxiliary contact is unused in thi...

Страница 10: ...e or the battery side by using the selector switch on front panel Powering the meter from the rectifier side default causes the PFM 500 to completely shutdown during a Low Battery Voltage Disconnect t...

Страница 11: ...8 Fax 714 856 9679 E Mail techservice newmarpower com PoweringTheNetwork com C LCD Display 1 Digital Meter Programming Sequence Flow Chart Figure 8 Digital Meter Programming Sequence Flow Chart see pa...

Страница 12: ...voltage disconnect Screen press programming button to enter set mode rotate knob to change push to confirm setting See page 13 for detailed directions 4B LVD voltage connect Screen press programming...

Страница 13: ...ngs and is retained even after powering down the unit LVD threshold adjustment can be made while the system is operating 3 LVD Alarms Pre disconnect disconnect Two external alarms can be triggered by...

Страница 14: ...Section III D for LVD adjustment procedure 4 PFM load circuit breaker tripped Breaker is in mid trip position Note Breaker will not activate the ALARM L E D if manually switched into the off position...

Страница 15: ...power com Anytime We are happy to consult with you to resolve any problems or questions you may have If during consultation it appears the PFM must be returned to the factory for repair we will issue...

Страница 16: ...low TEMPERATURE RATING 0 C to 60 C CASE SIZE H x W x D 3 5 x 19 or 23 x 20 5 LVD SPECIFICATIONS Factory set actuation voltages 12 Volt 24 Volt 48 Volt Disconnect 10 4V DC 21 0V DC 42 0V DC Connect 12...

Отзывы: