Two kits are available: QCK-3 for wiring up to three 24 or 48 volt Power Modules, and QCK-6 for wiring four to six 24 or 48 

volt modules. For more information or to order the quick connect kit, please contact the factory. For 12 volt model PM-12-

80, use model QCK-3A for up to three PM-12-80s and model QCK-6A for wiring four to six 

PM-12-80s .

Note: If using the QCK for Power Module/PFM wiring all Power Modules must be stacked in the rack, one atop another, above the 
PFM. (See FIGURES 3, 4 or 5) 

2) Standard Wiring Instructions

Up to six power modules with the same voltage output may be wired to the PFM input, with the total load current not to 

exceed 500 amps.
Refer to FIGURE 3 for the PFM input wiring instructions which follow.

FIGURE 3: Typical PFM DC Input Wiring

* Negative Ground Systems: Connect Ground Wire to (-) NEGATIVE OUTPUT Terminal and Hot Wire to (+) POSITIVE OUTPUT Terminal

* Positive Ground Systems: Connect Ground Wire to (+) POSITIVE OUTPUT Terminal and Hot Wire to (-) NEGATIVE OUTPUT Terminal

** Power Plugs shown present only if using NEWMAR QCK DC Quick Connect Kit, specify model QCK-3 (3 inputs) or 
QCK-6 (six inputs)

Figure 3 illustrates a typical input wiring confi guration with three power modules and one PFM (either positive or negative 

ground system).

1)

 “Hot” input wires are attached to the heavy duty bus bar labeled “INPUT (POWER MODULE)” on the rear of the PFM. 

Use the provided 1/4" hex head screws-washer-net sets. These may be replaced with 5/16" hardware if required for the 

installation.
Wiring should be terminated with ring lugs to ensure a safe installation. The ring lugs must make direct contact with the 

bus bar. If more than four units are wired to the PFM, lugs may be doubled up on the posts by removing the post fi rst, then 

reassembling the connection so that one lug seats against the bottom of the bus bar and the other against the top. Use an 

14 or 12 AWG

Return/Ground

Содержание PFM-500

Страница 1: ...ng E Output Wiring 5 1 Unswitched Output 2 Switched Output F Battery Wiring 6 G Status and Alarm Contact Wiring 7 H Chassis Grounding 8 I Circuit Breakers 8 1 Breaker Installation 2 Breaker Functions...

Страница 2: ...TERY POSITIVE NEGATIVE OR FLOATING GROUND STATUS CONTACTS RETURN GND INPUT 1 INPUT 2 INPUT 3 LVD SUMMARY ALARM OUTPUT INPUT 4 INPUT 5 INPUT 6 NC NO C CONTACTS SHOWN IN FAILED POSITION 1 2 3 1 2 3 1 2...

Страница 3: ...osing flush mounting C Bus Bar Mounting The PFM is shipped with a rackmount ground bus bar assembly kit BBA 800 The bus bar is typically mounted on the rear of the rack and is designed for installatio...

Страница 4: ...Hot Wire to POSITIVE OUTPUT Terminal Positive Ground Systems Connect Ground Wire to POSITIVE OUTPUT Terminal and Hot Wire to NEGATIVE OUTPUT Terminal Power Plugs shown present only if using NEWMAR QC...

Страница 5: ...for proper PFM input wire gauges 3 A return ground wire must also be run from the BBA bus bar or other grounding point to the terminal on the PFM labeled RETURN GND This is not a system ground rather...

Страница 6: ...s requires installation of a model PBA plug in breaker available from NEWMAR at that position See section II I Fig 7 for installation details and breaker functions See section VII for available ampera...

Страница 7: ...ness is designed for installations which employ NEWMAR Power Modules though it may be modified for use with other types of equipment as well provided they are equipped with Form C or Normally Open N O...

Страница 8: ...nd a summary alarm from the DST is required this may be accomplished through parallel wiring of the status wires Please contact the factory for information on how to perform this modification When wir...

Страница 9: ...reaker receptacle and pushing firmly into place The two top auxiliary contact terminals in the middle of the breaker should press against the mating clips The bottom auxiliary contact is unused in thi...

Страница 10: ...e or the battery side by using the selector switch on front panel Powering the meter from the rectifier side default causes the PFM 500 to completely shutdown during a Low Battery Voltage Disconnect t...

Страница 11: ...8 Fax 714 856 9679 E Mail techservice newmarpower com PoweringTheNetwork com C LCD Display 1 Digital Meter Programming Sequence Flow Chart Figure 8 Digital Meter Programming Sequence Flow Chart see pa...

Страница 12: ...voltage disconnect Screen press programming button to enter set mode rotate knob to change push to confirm setting See page 13 for detailed directions 4B LVD voltage connect Screen press programming...

Страница 13: ...ngs and is retained even after powering down the unit LVD threshold adjustment can be made while the system is operating 3 LVD Alarms Pre disconnect disconnect Two external alarms can be triggered by...

Страница 14: ...Section III D for LVD adjustment procedure 4 PFM load circuit breaker tripped Breaker is in mid trip position Note Breaker will not activate the ALARM L E D if manually switched into the off position...

Страница 15: ...power com Anytime We are happy to consult with you to resolve any problems or questions you may have If during consultation it appears the PFM must be returned to the factory for repair we will issue...

Страница 16: ...low TEMPERATURE RATING 0 C to 60 C CASE SIZE H x W x D 3 5 x 19 or 23 x 20 5 LVD SPECIFICATIONS Factory set actuation voltages 12 Volt 24 Volt 48 Volt Disconnect 10 4V DC 21 0V DC 42 0V DC Connect 12...