FURNACE LOCATION

IMPORTANT

Please read this entire manual and all labels before installing the furnace.

UNPACKING AND INSPECTION
It is the responsibility of the consignee of the unit to examine the packages for damage and, if found, to
note the same on the Carrier’s Bill of Lading.

The NH3 furnace is shipped in one package complete with oil burner, draft regulator, filter racks, air filters,
A/C Control Center (optional) and instruction manual. The LFR is shipped in two packages.

Caution: Remove shipping retaining bracket from blower before start-up.

HEAT LOSS

Before installation, verify the furnace output capacity meets the building heat loss requirements. A detailed
heat loss analysis is recommended.

INSTALLATION REGULATIONS

This unit should be installed in accordance with the regulations of the authority having jurisdiction. In
Canada the installation must conform to CSA Standard B139, "The Installation Code for Oil Burning
Equipment." In the United States, the National Fire Protection Association Standard NFPA 31 should be
followed. Check with provincial, state, or local codes concerning clearances, venting system
requirements and other regulations governing installation. Some codes may vary from the requirements
set forth in this manual.

FOUNDATION

To ensure the furnace is on a level foundation and above any possible dampness, a cement pad is
recommended.

CLEARANCES

The minimum clearances to combustible materials are as follows:

6"

Side

Rear

Top

Front*

Flue Pipe

Floor

NH-3

6”

6”

1”

24”

9”

Combustible

LFR

1”

2”

1”

16”

9”

Combustible

* Measured from the panel on which the burner is installed. Allow sufficient room for servicing.

FOR YOUR SAFETY: Do not store or use gasoline or flammable vapors and liquids in the vicinity of this or any
other appliance.

VENTING PRODUCTS OF COMBUSTION

CHIMNEYS

A negative overfire pressure should be maintained. Locate the furnace as close to the chimney or flue as
possible. The maximum draft is obtained by keeping elbows and pipe length to a minimum. Install the
flue pipe with a gradual rise of at least 1/4" per foot from the furnace to the flue. Do not extend the flue
pipe beyond the inside wall of the chimney. Refer to Table 11(a) and Table 11(b) for proper chimney flue
sizing and Fig. 23 for optimizing chimney draft.

The owner shall provide a chimney constructed to comply with the following specifications:

(a) The chimney must be absolutely smoke tight throughout its entire length, and must extend at least
three feet (3') above a flat roof or two feet above the ridges of peak roofs.

Содержание LFR-72

Страница 1: ...ING PRODUCTION Newmac Mfg Inc 208 LANCASTER CRESCENT P O BOX 9 DEBERT NOVA SCOTIA BOM 1G0 PHONE 902 662 3840 FAX 902 662 2581 WAREHOUSE Newmac Mfg Inc 430 SPRINGBANK AVE SOUTH WOODSTOCK ONTARIO N4V 1B...

Страница 2: ...X 24 2 MED LO LO LO 3 1 4 X 5 2 1 2 0 50 DIRECT DRIVE SPEED TAP BELT DRIVE MODEL AERO BURNER B T U H OUTPUT B T U H INPUT USGPH AFUE NOZZLE PUMP p s i INSERTION inches BURNER AIR SETTING AIR BAND CHI...

Страница 3: ...0 3 00 MED HI 1 010 1 280 3 00 MED HI 1 090 1 230 3 00 MED LO 920 1 115 2 75 MED LO 1 050 1 125 2 75 DELHI G10 8 DD 1 2 HP 4 SPD LO 845 0 50 900 2 25 DELHI G9 DD 1 2 HP 4 SPD LO 1 000 0 50 1 065 2 50...

Страница 4: ...2 3 Delavan 0 60 60A 145 2 1 5 4 4 0 02 380 20 x 25 MED HI 0 50 LO MED LO 0 20 LFR 73V BF3 73 000 83 640 0 60 81 9 Delavan 0 50 80B 145 2 1 3 8 0 02 350 20 x 25 MED LO HI 0 50 BURNER AIR DIRECT DRIVE...

Страница 5: ...erning installation Some codes may vary from the requirements set forth in this manual FOUNDATION To ensure the furnace is on a level foundation and above any possible dampness a cement pad is recomme...

Страница 6: ...with strong draft Follow the manufacturer s instructions located with the draft regulator for proper installation BLOCKED VENT SWITCH The WMO 1 blocked vent control is required on Newmac oil fired and...

Страница 7: ...of the same diameter and extend to the same depth in the tank An emergency oil shut off valve should be installed as required by local ordinance This can be manual electric solenoid or vacuum operated...

Страница 8: ...an Off Setting See Figs 2 3 and 4 This setting keeps the air circulation blower running until the temperature of the heat exchanger drops to the fan off temperature This ensures the blower adequately...

Страница 9: ...2 4x9 2 7 2 145 4x18 2 10 2 morethan725 Unconfined 21 4x6 1 5 1 21 4x6 1 5 1 725or less Confined 52 4x7 2 6 2 105 6x 9 2 8 2 NH3 LFR Freeareaof ductsassumesair isconveyedfromoutside The following shou...

Страница 10: ...on monoxide Ventilation may dilute any carbon monoxide produced under abnormal operating conditions Adequate air for combustion will help maintain the proper air fuel ratio Appliances which are burnin...

Страница 11: ...BURNER SET UP AND ADJUSTMENT The installer must use a suitable draft gauge smoke tester carbon dioxide tester 0 750 F stack thermometer 0 200 psi oil pressure gauge 0 30 in Hg vacuum gauge and 0 220 F...

Страница 12: ...cuum should be no more than 6 Hg Two pipe systems are recommended for lift feed or when the pump inlet is at a higher elevation than the tank outlet Install the return line termination higher than the...

Страница 13: ...sary The LFR has no cerafelt combustion chamber SMOKE BAFFLES Both the NH3 and the LFR furnaces have factory installed smoke baffles inside the radiator ducts NH3 Check to ensure they have not become...

Страница 14: ...er Similarly too much air during heating mode resulting in a temperature rise of less than 65 o F may cause heat exchanger degradation due to condensation DIRECT DRIVE BLOWER The installer should sele...

Страница 15: ...ot on the heat exchanger surfaces and firetube walls will reduce heat transfer and can increase fuel consumption significantly A 1 32 layer of soot acts as an insulator and can result in a 3 increase...

Страница 16: ...E 8 CONTACT SERVICE PERSONNEL FOR AIR FILTER REPLACEMENT 9 CONTACT SERVICE PERSONNEL BEFORE AND AFTER EXTENDED PERIODS OF APPLIANCE INOPERATION 10 THE BURNER IS FULLY AUTOMATIC IN OPERATION ALL ADJUST...

Страница 17: ...16 FIG 10 TYPICAL OIL TANK PIPING INSTALLATIONS...

Страница 18: ...17 FIG 11 DIMENSIONS CONTROL LOCATION NH3...

Страница 19: ...18 FIG 12 LFR SET UP...

Страница 20: ...19 FIG 13 STANDARD WIRING SCHEMATIC DIRECT DRIVE...

Страница 21: ...20 FIG 14 STANDARD WIRING SCHEMATIC A C READY DIRECT DRIVE...

Страница 22: ...21 FIG 15 STANDARD WIRING SCHEMATIC BELT DRIVE...

Страница 23: ...0 CFM 3 4 H P 1 H P 12 X 8 12 X 9 12 X 10 12 X 12 32 X 10 or 20 round 16 12 11 32 X 12 or 22 round 30 X 20 5 ton 2000 CFM 3 4 H P 1 H P 12 X 10 12 X 12 32 X 10 or 20 round 18 13 12 32 X 14 30 X 22 Min...

Страница 24: ...23 FIG 16 NH3 EXPLODED ASSEMBLY...

Страница 25: ...A 2040114 DIRECT DRIVE BLOWER DELHI G9 DD 33 41100140 BURNER CABLE 30 wire 18 conduit 21 B DIRECT DRIVE BLOWER TORIN DC 916 916 5 34 2200101 4 X 4 JUNCTION BOX 21 C 2040115 DIRECT DRIVE BLOWER DELHI...

Страница 26: ...rect Drive DD Blower Assembly 027 4010310 Stainless Steel Baffle 030 4050115 Blower Speed Junction Box Assembly Item No Part No Description 031 2010040 5uF 370v Capacitor 032 2040116T GT10DD or DCT 10...

Страница 27: ...26 FIG 18 RIELLO BURNER MODEL 40 F3 F5 EXPLODED ASSEMBLY FIG 19 RIELLO BURNER MODEL 40 BF3 BF5 EXPLODED ASSEMBLY Item 2030016 Riello Burner End Cone Protector not shown See Fig 9 for its location...

Страница 28: ...X O ring valve stem lower 17 12 3007268 X X X X Nozzle outlet fitting 18 14 3006553 X X X X Coil U bracket retainer nut 19 15 3002279 X X X X Coil 20 16 3007802 2060007 X X X X Pump 21 17 3000443 X X...

Страница 29: ...X Regulator assembly short 45 3006323 X X Regulator assembly short 46 46 3006330 X X Electrode assembly short 46 3006329 X X Electrode assembly short 47 47 3005869 X X X X Electrode porcelain 48 48 30...

Страница 30: ...nsformer 10 000 Volt 51771U 2090064 X Electronic Ignitor 14 000 Volt 17 3708 2090044 X Low Firing Rate Baffle 18 2090047 X 6 Electrode assembly 21 5770 X Junction Box Kit 26 3 666 X Knurled Locknut 27...

Страница 31: ...1 1 Fan 508 229 HF US S SV 7 35171223 2090011 1 Coupling 8 2060004 2060004 1 Pump 9 35382740 2090002 1 Transformer 2721 456 Electronic Ignitor 10 35141900 2110005 1 End Cone AFC 2X 2090020 2 End Cone...

Страница 32: ...60200 02 X Primary Control Interrupted Duty pre post purge 6 X Oil Valve in pump 7 22996 2060004 X Fuel Unit Std Single Stage Suntec A2VA 7116 8 34397 X Oil Line 3 16 OD Std Fuel Unit to Oil Valve 9...

Страница 33: ...32 FIGURE 23 COMMON CHIMNEY DRAFT PROBLEMS...

Страница 34: ...djust Air Settings Burner Locks out on Safety Poor Combustion Ensure Draft is Adequate Air Leak in Oil Supply Line Tighten Fittings or Replace Line Loose or Dirty Nozzle Replace Nozzle Faulty Oil Pump...

Страница 35: ...A Ducts Clear Blocked Return Registers Increase Undersized S A Ducts Clear Blocked Supply Grills Replace Faulty Blower Motor Clean Clogged Blower Wheel Tripping High Limit Replace Broken Blower Belt F...

Страница 36: ...C 4 OVERFIRE PRESSURE INCHES W C 5 NOZZLE ANGLE PATTERN 6 C02 PERCENT 7 BURNER MODEL 8 FLUE GAS TEMPERTURE FO 9 ROOM TEMPERTURE FO 10 SMOKE NUMBER BACHARACH 11 FUEL GRADE NUMBER 12 SUPPLY PLENUM STAT...

Страница 37: ...d from its published design or purpose and or an air conditioning coil shall not be installed on the return air side of the furnace 5 Furnace must not have been removed from the original installation...

Отзывы: