NX-1700E Card Reader
13
Segment 3
Door Fault Warning Time
Enter the amount of time a monitored zone (see Location 243, Segment 1) must be faulted before sounding a warning
(local buzzer). The door fault warning is timed in 1-second increments from 0 to 255 seconds. (Default is 30 = 30
seconds).
Segment 4
Door Fault Alarm Time
Enter the amount of time a monitored zone (see Location 243, Segment 1) must be faulted before sending an alarm
condition to the control panel. The door fault alarm is timed in 1-second increments from 0 to 255 seconds. (Default is 0
= disabled).
L
OCATION
245 R
ESETTING THE
R
EADER
A
DDRESS
(1 segment of numerical data) If it is necessary to reset the address of the reader, enter a 0 in this location.
This will cause the reader to cease functioning. If a card is scanned with the system in Program Mode,
the reader will again find an available address and set itself, beeping back to the user the address that
was found as per the table on page 5. If the system is not in Program Mode and a card is scanned at a
reader with a reset address, then it will sound an error beep.
L
OCATION
246 P
ROGRAMMING THE
A
CCESS
O
PTIONS
(2 segments of binary data)
Segment 1
Door Options
LED1 -
"On" if locking mechanism is a Maglock or Drop Bolt.
LED2 -
"On" if access is allowed regardless of Armed status of the system.
LED3 -
"On" if the door is not to be latched unlocked during an open schedule.
LED4 -
"On" if onboard open collector output only triggers during an open schedule.
LED5 -
“On” if onboard open collector output only triggers during a close schedule.
LED6 -
“On” if Forced Entry Alarm is logged.
LED7 -
“On” if access allowed without an RTE. (Default is “On”)
LED8 -
Reserved.
Segment 2
Enabling the Schedules for the Onboard Open Collector Output:
LED1 -
"On" if driver follows Schedule 1.
LED2 -
"On" if driver follows Schedule 2.
LED3 -
"On" if driver follows Schedule 3.
LED4 -
"On" if driver follows Schedule 4.
LED5 -
"On" if driver follows Schedule 5.
LED6 -
"On" if driver follows Schedule 6.
LED7 -
"On" if driver follows Schedule 7.
LED8 -
"On" if driver follows Schedule 8.
L
OCATION
247 P
ROGRAMMING THE
O
PENING
T
IME FOR
S
CHEDULE
1
(2 segments of numerical data)
Segment 1 Program the hour of the opening time in 24-hour format. (Default is 8 = 8:00 AM)
Segment 2 Program the minutes after the hour of the opening time for Schedule 1. (Default is 0)